Download Inhoudsopgave Inhoud Print deze pagina

Setting Procedure For The Expert Level - Siemens QAW740 Bedieningshandleiding

Inhoudsopgave

Advertenties

Beschikbare talen
  • NL

Beschikbare talen

  • DUTCH, pagina 13
Measured value adjustment for the room
temperature c
If there are deviations, the room temperature displayed can be set to
agree with the effective room temperature
Default value
Setting range
Forwarding the actual room temperature b
The adjusted actual value of the room temperature can be passed to
the bus system.
Default value
Setting choices
0 = do not send
1 = send
2.4

Setting procedure for the expert level

1. Press the Mode button for about 12
seconds until "prog" appears on the
display.
Installation Instructions
Display range
Actual value threshold of the room temperature
Using the threshold function, bus traffic of the room temperature can
be limited. In that case, a measured value is delivered only when the
threshold value is exceeded.
Default value
Range
Device address d
Note: When power is supplied to the room unit for the first time, an
automatic change to this display is made.
1.
Press the timer button
device address. If required, the setting knob can be used to
make individual settings.
2.
Press the Mode button
same time, entry of the address will automatically be checked.
If the entry was wrong, repeat the procedure.
For more detailed information about the device address, refer to the
description of the Konnex bus system, Data Sheet CE1N3127.
Default
Setting range
Installation Instructions
0 °C
-4.5...4.5 °C / -9...9 °F
1
0/1
74 319 0328 0 c - B1633
1...254
40 mK
20...300 mK
to start the search run for a free
to conclude this setting. At the
255
1...255
74 319 0328 0 c - B1633
2. Select the individual settings from the
following list by pressing the timer
button.
Exception: The „Device address" setting is quit by
pressing the Mode button. For more details, see
below.
3. Adjust the individual values with the
setting knob.
4.
After having made all settings, leave the
expert level by pressing the timer button.
Settings to be made on the expert level:
Programming mode
For setting the device address from a tool.
Display
Software version
Display
Device address of partner controller P
This shows the device address of the controller in the same
geographical zone (A). The room unit is the remote operation facility
for this controller.
7
8
74 319 0328 0 c - B1633
Operating Instructions
Do you want to start the timer function
for Comfort mode?
You can use the timer function to cover a period of
time selected by you. During that period of time,
continuous Comfort mode will be ensured.
1. Press the timer button
The time activated last for the end of the function
will appear.
2. Use the setting knob to set the required time to
the end of the function.
3. Wait until the display changes. The setting will
then automatically be saved.
To abort the timer function, press the Mode
button .
9
10
74 319 0328 0 c - B1633
prog
Software version
Installation Instructions
to start the function.
Operating Instructions

Advertenties

Inhoudsopgave
loading

Inhoudsopgave