Manual Mode

At any time, you can force a manual working mode useful for temporary use of the
system. If a password has been set (see parameter P16), the system will require it to
enable access to this feature.
1. Press the CAL key to enter the menu mode and use the ⇑ ⇓ keys to select the
option "MANUAL FUNC.1" (or "MANUAL FUNC.2").
2. Press CAL again to confirm.
3. Similarly, proceed for pump 2.
4. Press ESC at any time to exit the manual mode.
Warning! In manual mode, only one pump at a time can be activated.

Control Examples

Typical Application in Swimming Pool Control: Acidification
● Acidification when pH exceeds the pH value of 7.30. Refer to the "List of
configuration parameters" and set:
● P01 ON/OFF working mode for pump 1
● P02 set-point 7.30 pH
● P04 dosage direction "ACIDIFICATION"
● P11 alarm pump 1 = 60 minutes

Typical Application in Swimming Pool Control: Chlorination

● Chlorination when ORP potential falls below 680 mV. Refer to the "List of
configuration parameters" and set:
● P06 PROPORTIONAL working mode (recommended for an easier
stabilization)
● P07 set-point 680 mV
● P09 dosage direction "CHLORINATION"
● P10 if the quantity of the product to be injected is not known, it is
recommended to start with a time base of 60 seconds (default) and if

Advertenties