Terminal assign-
For grounded solar modules, only the ungrounded poles of the solar module strings may
ment for ground-
be connected to the fuse-protected terminals (A).
ed solar modules
Negative solar module ground
Positive solar module ground
Example of termi-
nal assignment
for grounded so-
lar modules
Assignment for solar module ground at the negative
pole
Connecting Solar
1
Module Strings to
the Fronius String
Control 100/12
(A)
(B)
(C)
-
+
B'
A'
(
)
(
) (
)
(
)
B
A
(B)
(A)
Tightening torque 2.0 Nm
Tightening torque 1.5 Nm
Tightening torque 2.0 Nm
DC-
DC+
B (in)
B' (out) A' (out)
DC+
DC-
B (in)
B' (out) A' (out)
+
B'
A'
(
)
(
) (
B
Assignment for solar module ground at the positive
pole
2
(A)
A (in)
A (in)
-
)
(
)
A
(C)
67