Parameters
6-92 Terminal 42 Digital Output
Option:
[42]
Above ref, high
[45]
Bus Control
[60]
Comparator 0
[61]
Comparator 1
[62]
Comparator 2
[63]
Comparator 3
[64]
Comparator 4
[65]
Comparator 5
[70]
Logic rule 0
[71]
Logic rule 1
[72]
Logic rule 2
[73]
Logic rule 3
[74]
Logic rule 4
[75]
Logic rule 5
[80]
SL digital output A
[81]
SL digital output B
[82]
SL digital output C
[83]
SL digital output D
[160] No alarm
[161] Running reverse
[165] Local ref. active
[166] Remote ref. active
[167] Start command activ
[168] Drive in hand mode
[169] Drive in auto mode
[193] Sleep Mode
[194] Broken Belt Function
[196] Fire Mode
[198] Drive Bypass
6-93 Terminal 42 Output Min Scale
Range:
Functie:
0 %
[0 - 200
Schaling voor de minimale uitgangswaarde (0
*
%]
of 4 mA) van het analoge signaal op klem 42.
Stel de waarde in als een percentage van het
volledige bereik van de variabele, dat is
ingesteld via 6-91 Terminal 42 Analog Output.
6-94 Terminal 42 Output Max Scale
Range:
Functie:
100
[0 -
Schaal de maximale uitgangswaarde (20 mA) van
%
200
de schaling op klem 42. Stel de waarde in als een
*
%]
percentage van het volledige bereik van de
variabele, dat is ingesteld via 6-91 Terminal 42
Analog Output.
VLT® HVAC Basic Drive Programmeerhandleiding
Functie:
MG18B210 – VLT® is een gedeponeerd handelsmerk van Danfoss
6-94 Terminal 42 Output Max Scale
Range:
Functie:
Current
(mA)
20
0/4
0%
Analogue
output
Min Scale
par. 6-93
Afbeelding 3.12
6-96 Terminal 42 Output Bus Control
Range:
0
[0 - 16384 ]
*
Analogue
100%
Variable
Output
for
Max Scale
output
par. 6-94
example:
Power
Functie:
61
3
3