Wire colour
C1
brown
C2
yellow
C3
green
C4
white
Modbus messages
Modbus
Description
address
1000 Modbus slave address
4009 Temperature from atmosphere [°C]
4010 Temperature from dwelling [°C]
4011 Pressure supply duct [Pa]
4012 Pressure exhaust duct [Pa]
3
4013
4014
4015
4021 Parameter imbalance allowed
4027 Parameter preset imbalance [m
4028
4029
4030 Bypass valve status
4036 Parameter bypass mode
4037 Preheater status
4038
4039 Current fault code
4040 Filter message
4046 Parameter: Geo heat exchanger mode
4052 Parameter: Geo heat exch. min. temp.[°C]
4058 Parameter: Geo heat exch. min. temp.[°C]
4059 Index selected CO
2
sensor
2
4060
sensor [PPM]
4999 Error message
6001
6002
6003
6004 Parameter: Imbalance allowed
6005 Parameter: Preset imbalance [m
6006 Parameter: Bypass mode
6007 Command: Filter reset
6008 Parameter: Geo heat exchanger mode
6009 Parameter: Geo heat exch. min. temp. [°C]
6010 Parameter: Geo heat exch. max. temp. [°C]
6012
6013 Command: Set control mode
Art.-nr.: 611885-D
Control pcb in
Cable-mounted
edge connector
connecting cable
C4
4
C3
3
C2
2
C1
1
function
correction
code
factor
0x06
1
0.1
0.1
1
1
1
1
1
1
3
1
3
1
3
1
0x03
1
1
1
1
1
1
1
0.1
0.1
1
1
1
3
1
1
1
1
3
1
1
0x06
1
1
0.1
0.1
1
1
Modbus Interface
Connect
Factory
setting
jumpers
signed Values
no
yes
yes
no
no
Function code 0x03 = read action
no
Function code 0x06 = write action
no
no
no
yes
no
no
no
no
no
no
no
no
no
0= Off, 1 = On
yes
4027, 4036, 4046, 4052 & 4058
yes
are only valid after the parameter in
no
question has been stored!
no
no
no
no
no
no
yes
no
no
1
no
0= Off, 1 = On
yes
yes
no
1
no
Connectors Brink
Connect screwa-
ble up to 1.5 mm²
I2C <> Modbus
Green LED
power supply
pwr
Modbus
system
C4
C3
C2
C1
GB
5