software version from S1.06.05) and a Modbus network. The interface comes with a 1 m long connecting cable for connecting the
Application
way products or installations that do not have a Modbus interface as standard can still be incorporated into a Modbus network using
a (free) I2C interface.
Then a new Modbus slave address between 1 and 247 can be entered at register address 1000, using function code 0x06, write
single register When entered correctly, the Modbus slave address will directly be active.
Bus module Interface
Dimensions WxHxD
Connection
Housing
Weight
Storage temperature
Power consumption
Installation position
Interfaces
Protection class
Power supply
Module status display
System bus
Ambient operating temperature
89.7
The modules come with a default Modbus Slave address, viz.
0x0B.
4
Dimensions WxHxD 36 x 89.7 x 62.2 mm
Connection through screw plug terminals up to 1.5 mm²
Weight ca. 100 g
Storage temperature -10...+70 °C
Power consumption 0.2 W
Class 3K3
Installation position on vertical surfaces (wall installation, connectors top and bottom)
Protection class IP 20
Power supply indication by green LED
+5...+40°C
36
Communication parameters Modbus:
Modbus Interface
Connector
no.
1
2
3
I2C <> Modbus
4
5
pwr
6
Function
GND system voltage
I2C bus Serial Data (SDA)
I2C bus Serial Clock (SCL)