Modbus asetukset

Parametri
Tiedonsiirtonopeus
Pariteetti
Lopetusbitit
Modbus mode

Modbus rekisterit

Säilytysrekisterin luku/kirjoitus käyttämällä Modbus-toimintoa 3,
Nimi
On/Off
Date - Year
Date - Month
Date - Day
Time - Hour
Time - Minute
Time - Second
Start time - Hour
Operating time
Initial operating time
Safety valve pressure
Reserved
Min pressure
Reserved
Reserved
Reserved
Alarm type
Input rekisterit
Nimi
Pressure
Reserved
Reserved
Total pump start count high
Total pump start count low
Stop reason
Reserved
Reserved
Reserved
Reserved
Log entry 1 (newest) – Month
Log entry 1 (newest) – Day
Log entry 1 (newest) – Hour
Log entry 1 (newest) – Minute
Log entry 1 (newest) – Code
Log entry 2 – Month
Log entry 2 – Day
Log entry 2 – Hour
Log entry 2 – Minute
Log entry 2 – Code
For log entry 3-6 use address 20-24, 25-29, 30-34, 35-39. For more information see www.ttmenergi.com.
20
C650
®
Arvo
9600
None
1
RTU
Osoite
Read/Write
0
Read/write
1
Read/write
2
Read/write
3
Read/write
4
Read/write
5
Read/write
6
Read/write
7
Read/write
8
Read/write
9
Read/write
10
Read/write
11
Read/write
12
Read/write
13
Read/write
14
Read/write
15
Read/write
16
Read/write
Osoite
Read/Write
0
Read
1
Read
2
Read
3
Read
4
Read
5
Read
6
Read
7
Read
8
Read
9
Read
10
Read
11
Read
12
Read
13
Read
14
Read
15
Read
16
Read
17
Read
18
Read
19
Read
Slöjdaregatan 1 | 393 66 Kalmar | Sweden | Puh: + 46 480 41 77 40 | info@ttmenergi.se | www.ttmenergi.se
Kommentti
Read/set whether the device is started/stopped
Read/set year for system date
Read/set month for system date
Read/set day for system date
Read/set hour for system time
Read/set minute for system time
Read/set second for system time
Read/set hour for start time of the degassing
Read/set number of hours per degassing run
Read/set initial run time in number of days
Read/set the safety valve's pressure in mbar
Reserved, reads as 0
Read/set lower target threshold for pressure
Reserved, reads as 0
Reserved, reads as 0
Reserved, reads as 0
Read/clear alarms
Kommentti
Present pressure in mbar
Reserved, reads as 0
Reserved, reads as 0
Total number of pump starts, most significant 16 bits
Total number of pump starts, least significant 16 bits
Reason for system not running
Reserved, reads as 0
Reserved, reads as 0
Reserved, reads as 0
Reserved, reads as 0
Month for log entry 1 (newest)
Day for log entry 1 (newest)
Hour for log entry 1 (newest)
Minute for log entry 1 (newest)
Code for log entry 1 (newest)
Month for log entry 2
Day for log entry 2
Hour for log entry 2
Minute for log entry 2
Code for log entry 2