Power on the System / Schalten Sie das System ein / Mise sous tension du système
/ Encienda el sistema / Ligue o sistema / Het systeem inschakelen / Accensione del
sistema / Włączanie systemu / Zapnutí systému / Slå på systemet / Pornire sistem
/ Включване на системата / Tænd for systemet / Ρεύμα στο σύστημα / Süsteemi
sisselülitamine / Kytke järjestelmän virta päälle / Napajanje sustava / Rendszer áram
alá helyezése / Įjungti sistemą / Ieslēdziet sistēmu / Zapnite system / Vklopite sistem /
Sistemin Gücü / Ligar o sistema
Note!
Regarding the first start, after pressing and holding the POWER button on the battery pack that
1.
connects to the inverter for 15 seconds, the battery system will assign each battery pack in a
communication loop a unique address (battery number). In the meantime, the status light will remain on
solid yellow for the first 11 seconds and then turn to solid green light, and the SOC power indicators will
remain on solid blue based on the battery pack's actual battery capacity. After 15 seconds, the status light
will flash yellow, and at the same time, release the button. In the meantime, the unique address (battery
number) will be assigned. The status light will turn to flash green or solid green after finishing the address
assignment. Then the user can press the button to shut down the system.
2.
Regarding the second start, after pressing the POWER button on the battery pack that connects to the
inverter for less than 3 seconds, the status light remains on solid yellow light at the first 11 seconds and
then turns to solid green light. In the meantime, the SOC power indicators remain on solid blue light
based on the battery packs' actual battery capacity. At this point, release the button.
In the event that the user wishes to increase or reduce the battery packs, the system must be turned off.
3.
After completing the capacity expansion or reduction, press and hold the POWER button for more than
15 seconds to reassign each battery pack in communication loop a unique address.
4.
In the event that the inverter purchased by the user is one of the models specified in PYLON CANBUS
Protocol, the user must continuously press the POWER button 3 times within 10 seconds to power on
the battery. After a successful power-on,
a.
If the battery is running properly, it will be charging all the time.
b.
If there is any fault, the battery will be power off first and then automatically powered on again after
such a fault has been resolved.
5.
A system problem may be encountered while pressing the button frequently. The user may need to wait