Unit with electrical heating
The electrical installation is made on
the top of the unit, fig.2. The 3 kW unit is
connected via the integrated control card
using a 1,5 m cable and plug. Other units are
intended for permanent installation. Control
supply (230V~) and power supply for heating
(400V3~) are connected to terminal block
in the internal connection boxes. 2-metre
units require dual power supplies. The largest
cable diameter for the terminal block is
16 mm². The cable glands used must meet
the protection class requirements. In the
distribution board it is to be indicated that
"the air curtains can be supplied from more
than one connection".
See wiring diagrams.
Type
Output
[kW]
Control
0
PA2210CE05
5
8
PA2215CE08
PA2215CE12
12
PA2220CE10
10
PA2220CE16
16
)Dimensioning of external wiring shall comply with applicable
*1
regulations and local deviations may occur.
26
PA2200C
Voltage
Minimum
[V]
area
*1
[mm
]
2
230V~
1,5
400V3N~ 1,5
400V3N~ 2,5
400V3N~ 4
400V3N~ 2,5
400V3N~ 6
Start-up (E)
When the unit is used for the first time or
after a long period of disuse, smoke or odour
may result from dust or dirt that has collected
on the element. This is completely normal
and disappears after a short time.
Connecting the water coil (W)
The installation must be carried out by an
authorised installer.
The water coil has copper tubes with
aluminium louvres and is suitable for
connection to a closed water heating system.
The heating coil must not be connected to
a mains pressure water system or an open
water system.
Note that the unit shall be preceded by a
regulating valve, see Frico valve kit.
The water coil is connected on the upper
side of the unit with ø15 mm smooth copper
pipe with a suitable coupling or soldering.
The connections to the heating coil must be
equipped with shut off valves (not included)
to allow problem free removal. Water coil is
equipped with a drain valve.
A vent valve should be connected at a high
point in the pipe system. Air valves are not
included.
NOTE: Care must be taken when connecting
the pipes. Use a wrench or similar to hold the
air curtain connections to prevent straining
of the pipes and subsequent water leakage
during connection to water supply pipe-work.
Adjustment of the air curtain and air flow
The direction and speed of the air flow should
be adjusted considering the load on the
opening. Pressure forces affect the air stream
and make it bend inwards into the premises
(when the premises are heated and the
outdoor air is cold).
The air stream should therefore be directed
outwards to withstand the load. Generally
speaking, the higher the load, the greater the
angle that is needed.
Basic setting fan speed
The fan speed when the door is open is set
using the control. Note that the air flow
direction and fan speed may need fine
adjustment depending on the loading of the
door.