Electric supply connections
•
Cut the electricity supply before any work inside the appliance (risk of electric shock). The removal of the power
supply has to be such that you can always check from any of the points to which you have access that the power
supply remains removed. If this is not possible, you should provide a disconnection with a locking system.
•
Only a qualified and experienced technician is authorised to carry out cabling work within the appliance or to
replace the power cord.
•
Make sure that the terminal screws are fully tightened (risk of fire). Incorrectly tightened terminal screws will cancel
the warranty.
•
Do not disconnect the electricity supply when the appliance is running. If the electric power supply is interrupted,
wait a minute before restoring the power.
Connect the unit to the power supply and options
Open the top panel with a screwdriver (4 screws) to access the electrical terminal
block. Insert the power supply cable
part of the appliance. Inside the appliance, fix the power supply cable by threading
it through the cable clamp
Connect the power supply cable to the terminal block inside the appliance as
following.
Connect options
Connect to
(filtration pump,
power supply
power supply relay).
Terminal block for single phase power supply
Cable wiring and protection
Electricity
Model
supply
Eco Elyo-05
Eco Elyo-07
Eco Elyo-09
Eco Elyo-13
220 - 240 V
1 phase
Eco Elyo-15
50-60 Hz
Eco Elyo-20
Eco Elyo-24
Eco Elyo-30
Eco Elyo-20T
380 - 400 V
Eco Elyo-24T
3 phase
50-60 Hz
6
Eco Elyo-30T
*Cable cross section suitable for max. length 20 meters.
into one of the cable gland
.
Connect
to power
supply
Terminal block for tri-phase power supply
Max.
Cable diameter*
current
8
RO2V 3x2,5 mm
9
13
16
19
RO2V 3x4 mm
21.7
30
RO2V 3x6 mm
7.9
RO2V 5x2,5 mm
9.4
13
RO2V 5x4 mm
on the rear
L: Live
N: Neutral
: Earth
Connect options
(filtration pump,
power supply relay)
²
²
²
²
²
Heating priority connection
P2 P1
1 -
2: Power for the filtration
pump power contactor coil
: filtration timer
: power contractor (two-pole contac-
tor) for filtration system pump motor
: separate cable for the "heating
priority" function (not supplied)
: heat pump terminal board
: fuse
230V/dry contact relay (not
:
included)
Thermal magnetic protection
16 A
20 A
25 A
32 A
10 A