PRESENTATION
This product is a detector designed to identify gas leaks.

GAS DETECTOR DESCRIPTION

Main features:
- High reliability sensor
- Automatic reset after alarm
- Detects natural gas, LPG (liquefied petroleum gas) and coal gas
- Indoors only usage

TECHNICAL SPECIFICATIONS OF GAS DETECTOR

Supply voltage
Output voltage for the solenoid valve
Standby consumption
Alarm consumption
Maximum consumption
Sensor priming time
Sound intensity
Alarm level
Gas density alarm level
Operating temperature
Dimensions

INSTALLATION INSTRUCTIONS

1. First identify whether the gas is heavier or lighter than the air. Gases heavier than air: LPG etc. Gases lighter
than air: natural gas, methane gas, etc.
2. Depending on the weight of the gas, choose the correct location of the gas detector. If the gas is heavier than
air, position the gas detector at 0.3 - 1.0 m from the floor, within a radius of max. 1.5 m from the combustion
source (eg stove). If the gas is lighter than air, position the gas detector at 0.3 - 1.0 m from the ceiling, within a
maximum radius of 1.5 m from the combustion source (eg stove).
3. Secure the screws to the wall, then position the gas detector.
230V
9 - 12V (impulse)
≤ 90mA
≤ 100mA
3W (la 230V)
about 180 seconds
≥ 70dB/m
20% LEL (Lower Explosive Limit)
0.1% - 0.5%
-26°C ~ +80°C
115 x 72 x 41 mm
3