8. Test run
8.1. Before test run
► After completing installation and the wiring and piping of the indoor and
outdoor units, check for refrigerant leakage, looseness in the power supply
or control wiring, wrong polarity, and no disconnection of one phase in the
supply.
► Use a 500-volt megohmmeter to check that the resistance between the
power supply terminals and ground is at least 1 MΩ.
► Do not carry out this test on the control wiring (low voltage circuit) termi-
nals.
en
WARNING:
Do not use the outdoor unit if the insulation resistance
is less than 1 MΩ.
Insulation resistance
After installation or after the power source to the unit has been cut for an extended
period, the insulation resistance will drop below 1 MΩ due to refrigerant accumulat-
ing in the compressor. This is not a malfunction. Perform the following procedures.
1. Remove the wires from the compressor and measure the insulation resistance of
the compressor.
2. If the insulation resistance is below 1 MΩ, the compressor is faulty or the resist-
ance dropped due the accumulation of refrigerant in the compressor.
3. After connecting the wires to the compressor, the compressor will start to warm
up after power is supplied. After supplying power for the times indicated below,
measure the insulation resistance again.
8.2. Test run
8.2.1. Using remote controller
Refer to the indoor unit installation manual.
Note :
Occasionally, vapor that is made by the defrost operation may seem as if smoke come up from the outdoor unit.
9. System control
Set the refrigerant address using the DIP switch of the outdoor unit.
SW1 Function Setting
Refrigerant
SW1 Setting
address
ON
00
OFF
3 4 5 6 7
ON
01
OFF
3 4 5 6 7
ON
02
OFF
3 4 5 6 7
10. Specifications
Outdoor model
Power supply
Dimensions (W × H × D)
Sound Power Level *1 (Heating) dB(A)
*1 Measured under rated operation frequency.
14
Refrigerant
SW1 Setting
address
ON
03
OFF
3 4 5 6 7
ON
04
OFF
3 4 5 6 7
ON
05
OFF
3 4 5 6 7
PUZ-WM50VHA
V / Phase / Hz
mm
950 × 943 × 330
61
• The insulation resistance drops due to accumulation of refrigerant in the com-
pressor. The resistance will rise above 1 MΩ after the compressor is warmed
up for 4 hours.
(The time necessary to warm up the compressor varies according to atmos-
pheric conditions and refrigerant accumulation.)
• To operate the compressor with refrigerant accumulated in the compressor,
the compressor must be warmed up at least 12 hours to prevent breakdown.
4. If the insulation resistance rises above 1 MΩ, the compressor is not faulty.
CAUTION:
• The compressor will not operate unless the power
supply phase connection is correct.
• Turn on the power at least 12 hours before starting
operation.
-
Starting operation immediately after turning on the main power switch can result
in severe damage to internal parts. Keep the power switch turned on during the
operational season.
► The followings must be checked as well.
• The outdoor unit is not faulty. LED1 and LED2 on the control board of the outdoor
unit flash when the outdoor unit is faulty.
Note:
a) Up to 6 units can be connected.
b) Select one single model for all units.
c) For Dip switch setting for indoor unit, refer to the indoor unit's installation
manual.
PUZ-WM60VAA
PUZ-WM85VAA
230 / Single / 50
58
PUZ-WM112VAA
PUZ-WM85YAA
400 / Three / 50
1050 × 1020 × 480
60
58
PUZ-WM112YAA
60