Counters
Counter values of the device:
•
•
•
6.1.4
Unit state
/i
State
Description
Device turned OFF The unit is switched off
Standby
The unit is not operating and
waiting for a starting command
Pump test
The pump is running. The system
valve will stay open
Degassing
The unit is degassing
Refill
The unit is refilling
Manual refill
Refill the unit manually
Stopping
The system valve will open
Error
The unit has stopped because a
critical error has occurred
6.1.5
User settings
/i
General settings
Parameter
Description
Language
The language of the display texts
Date and Time
The actual date and time
System fluid
•
•
Boiler interlock
External connections/interfaces
can be programmed to open when
pressure drops below or rises
above a critical boiler limit.
These limits can be set after
selecting the boiler interlock
option.
17
Total degass time (in hours)
Total refill time (in hours)
Total refill volume (in liters)
Water
Water glycol mixture
General settings
Parameter
Common fault
/i
Degassing settings
Parameter
Auto degass time
1
Auto degass time
2
Block time
/i
Refill settings (only for S400-R and S400-B versions)
Parameter
Refill volume
alarm after
Refill time alarm
after
Max. refill
frequency
English
Description
Contact for communicating a
fault.
Contact is normally open (NO) by
default, but can be switched to
normally closed (NC).
In situations that the common
fault contact is NC, switching off
the mains power will make this
contact NO as long as the power is
switched off.
Description
Time setting for daily start time
and stop time of the degassing
process.
Second time setting for daily start
time and stop time of the
degassing process.
Time for stopping the degassing
process.
Weekday (every day of the
•
week can be chosen)
Year (max. 5 periods per year
•
can be chosen)
Description
Maximum allowed refill quantity
per refill. Issues an alarm if a refill
exceeds this threshold.
Range: 0 - 2500 l; 0 = switched
off.
Maximum continuous refill time.
Range: 0 - 255 min.; 0 = switched
off.
Maximum number of times per
day that refilling is allowed
Range: 0 - 10 times; 0 = switched
off.
User manual - 1.0