The brightness value can be set by manual
operation on the device or by the programmed
dimming button of an operating unit.
Set switch (1) to max. in order to apply the set
brightness as maximum dimming value.
Or:
Set switch (1) to min. in order to apply the set
brightness as minimum dimming value.
Keep the operation button (7) pressed for more
than 3 s.
The status LED flashes twice. The set bright-
ness value is saved.
If the minimum or maximum dimming value are
outside the setting range, the status LED (7)
flashes permanently after the save operation.
Setting dimming mode on the device
In the factory setting, the device performs an
automatic load detection for ohmic, inductive and
capacitive loads and selects the suitable dimming
performance. If the load type is known, this can
be specified on the device without performing an
automatic load detection.
The device is ready for operation.
Keep the dimming mode button (2) pressed
until its own illumination flashes.
Select the channel for which you wish to
change the dimmer mode by pressing on button
(7).
Briefly press the dimming mode button (2)
repeatedly until the coloured lighting of the
button (2) displays the desired operating mode
(Table 3).
Keep the dimming mode button (2) pressed
until the lighting of the button (2) flashes quickly.
While the button is flashing quickly, the selected
operating mode is set. After that, the operating
mode is displayed for approx. 3 s before the
button goes out.
If the setting is not confirmed by holding down
the button, the device will revert to its previous
dimming mode after 2 minutes.
If the operating mode selected is not suitable
for the connected load, the dimming channel
will reset to „factory setting" automatically.
Lighting
Dimming mode
button (2)
yellow
Energy-saving lamps (CFL)
purple
Capacitive load
blue
Inductive load
red
LED load
green
taught-in load (CFL + LED)
white
automatic load setting (factory
setting)
1) The load for the selected dimming mode is only taught
in for approx. 30 s. This can lead to temporary impair-
ment of the lighting.
Table 3
Displaying dimming mode
A single press on button (2) followed by a press
on button (7) of the channel concerned, allows
the current dimmer mode to be consulted.
The coloured lighting of the button will display
the current operating mode for approx. 3 s
(Table 3).
Teach in the load of an operating unit via the
button
When teaching in the connected load, the dimming
performance for compact fluorescent lamps and
LED lamps is optimised.
All manuals and user guides at all-guides.com
The device is ready for operation. The dimming
button of an operating unit has been programmed
with the taught-in output.
Press the dimming button 5 times briefly, then
keep the button pressed until the load switches
off.
The short press is independent of the config-
ured operating performance on the operating
unit ( 5 x On, 5 x Off or 5 x On/Off).
Press button once briefly.
The teach-in process starts. The teach-in
process lasts approx. 30 s. A dimming operation
is performed to optimise the dimming perfor-
mance. After teaching in, the connected load
lights up at maximum brightness and flashes
once. The teach-in process is complete.
Depending on the connected load, the minimum
brightness may change due to the teach-in
process.
Resetting taught-in loads in the device
The device can be reset to automatic load detec-
tion, e.g. after replacing illuminants.
Automatic load detection is particularly suitable
for loads that can be dimmed clearly in the
phase cut-on or phase cut-off („conventional
loads").
The device is ready for operation. The dimming
button of an operating unit has been programmed
with the taught-in output.
Press the dimming button 5 times briefly, then
keep the button pressed until the load switches
off.
The short press is independent of the config-
ured operating performance on the operating
unit ( 5 x On, 5 x Off or 5 x On/Off).
If the dimming button is no longer pressed with-
in the next 10 seconds, the learned dimming
principle is retained.
Press button 2 times briefly.
The load flashes 2 times. The automatic load
detection is enabled again.
Appendix
Technical data
Supply voltage
via mains
Mains frequency
1)
Energy dissipation
Supply voltage KNX/EIB
Current consumption KNX/EIB
Consumption without load
1)
Upstream protection: circuit breaker
Operating altitude
Pollution degree
Surge voltage
Degree of protection of housing
Degree of protection of housing under front panel
IK (impact protection)
Overvoltage class
Dimension
Connection capacity
Operating temperature
Storage temperature
Communication media KNX
Configuration mode
Conventional and electronic transformers
should not be operated with less than 75% of
their nominal load.
Troubleshooting
Manual operation not possible
Cause 1: switch (1) not moved to
Move switch to
Cause 2: manual operation has not been enabled
(Systemlink)
Enable manual operation via application soft-
ware.
Connected loads to not light up
Cause1: electronic short-circuit and overload
protection has triggered, control LED (8) lights up/
flashes.
Reduce connected load, check wiring and
repair if necessary.
Cause 2: overheating protection has triggered,
control LED (9) lights up.
Reduce connected load, provide sufficient cool-
ing, increase distance to adjacent devices.
Bus operation is not possible
Cause 1: bus voltage is not present.
Check bus connection terminals for correct
polarity.
Check bus voltage by briefly pressing the
programming button (6), red LED lights up
if bus voltage is present. If mains voltage is
available without bus voltage, the red LED is lit
up permanently.
Cause 2: manual operation is active. Switch (1) is
in position
Move switch (1) to position auto.
Warranty
We reserve the right to make technical and formal
changes to the product in the interest of technical
progress.
Our products are under guarantee within the scope
of the statutory provisions.
If you have a warranty claim, please contact the
point of sale or ship the device postage free with a
description of the fault to the appropriate regional
representative.
230V~ +10/-15%
240V~ +6/-6%
50/60 Hz
8.9 W
(Applicable in the European Union and other European
countries with separate collection systems).
21-32V s SELV
This marking shown on the product or its literature
2.3 mA
indicates that it hould not be disposed with other
600 mW
household wasted at the end of its working life. To prevent
possible harm to the environment or human health from
10 A
uncontrolled waste disposal, please separate this from
2000 m max.
other types of wastes and recycle it responsibly to
promote the sustainable reuse of material resources.
2
Household users should contact either the retailer where
4 kV
they purchased this product, or their local government
IP20
office, for details of where and how they can take this item
for environmentally safe recycling.
IP30
Business users should contact their supplier and check
04
the terms and conditions of the purchase contract. This
product should not be mixed with other commercial
III
wastes of disposal.
6 modules, 6 x 17.5 mm
0.75 mm²...2.5 mm²
Usable in all Europe
-5 ...+ 45°C
- 20 ...+ 70°C
TP 1
S-Mode, easy link
controller (8031 30 07)
.
.
.
Correct Disposal of This product
(Waste Electrical & Electronic
Equipment).
å
and in Switzerland
6LE000489C - 12/2016