Operation
Manual operation
Bus or mains power supply is present.
Push switch (1) to position
Manual operation is switched on, the output can
be controlled using the operation button (7).
During manual operation, the controller is deac-
tivated via the KNX bus.
Systemlink start-up:
Depending on the programming, the manual
operation is either activated permanently or for
a time period configured via the application soft-
ware. If the manual operation is disabled via the
application software, no activation takes place.
Or:
Move switch (1) to position auto.
The manual operation is switched off. Operation
takes place solely via the KNX bus. The output
adopts the brightness predefined by the bus
controller.
Operating output in manual operation
Operation takes place by a short or long press on
the operation button (table 1).
If the integrated LED flashes when pressing the
operation button, no load is connected.
Status
Performance when pressing
the button
Load is switched
Short press on button:
off.
Switch ON the connected load.
LED lights up.
Status LED of
the button (7)
Long press on button:
is off.
Dim up to maximum brightness.
Status LED of the button (7)
lights up.
Load is switched
Short press on button:
on.
Switch OFF the connected load.
Status LED (7) of the button
Status LED of
goes out.
the button (7)
lights up.
Long press on button:
Changes the current bright-
ness. Dimming takes place in
the opposite direction of the last
dimming operation until maxi-
mum or minimum brightness.
Table 1: Manual operation
Information for electricians
Installation and electrical connection
DANGER!
ç
Touching live parts can result in an
electric shock!
An electric shock can be lethal!
Disconnect the connecting cables
before working on the device and
cover all live parts in the area!
CAUTION!
ç
Impermissible heating if the load of
the device is too high!
The device and the connected cables
may get damaged in the connection
area!
Do not exceed the maximum current
carrying capacity!
All manuals and user guides at all-guides.com
Observe temperature range. Provide sufficient
cooling.
Mount device onto DIN rail in accordance with
DIN EN 60715.
.
Connect device
Fig 2: Installation/deinstallation with plug-in
(11) Load
Connect bus cable via connecting terminal (3).
Connect load (11) on the lower terminal strip (4)
of the device.
terminals
Quickconnect
ε
(11)
Cha rge
Fig 3: Device connection
Start-up
Systemlik: Loading the physical address and
application software
The switch for manual operation (1) is in position
auto.
Switch on bus voltage.
Press programming button (5).
The button lights up.
If the button does not light up, no bus voltage is
present.
Load the physical address into the device.
Status LED of the button goes out.
Load application software.
Note down the physical address on the labelling
field (5).
Easylink:
Information on the system configuration can be
taken from the extensive description of the service
module easylink.
Start up the device.
Switch on mains supply.
Functional test
The functionality of the outputs is displayed via the
status LED of the operation button (7).
LED status
Meaning of the signal
LED lights up
Load is activated
permanently
LED flashes
No load connected
Setting minimum and maximum dimming value
on the device
The device is ready for operation.
Setting brightness value
The brightness value can be set by manual
operation on the device or by the programmed
dimming button of an operating unit.
Set switch (1) to max. in order to apply the set
brightness as maximum dimming value.
Or:
Set switch (1) to min. in order to apply the set
brightness as minimum dimming value.
Keep the operation button (7) pressed for more
than 3 s.
The status LED flashes twice. The set bright-
ness value is saved.
If the minimum or maximum dimming value are
outside the setting range, the status LED (7)
flashes permanently after the save operation.
Setting dimming mode on the device
In the factory setting, the device performs an
automatic load detection for ohmic, inductive and
capacitive loads and selects the suitable dimming
performance. If the load type is known, this can
be specified on the device without performing an
automatic load detection.
The device is ready for operation.
Keep the dimming mode button (2) pressed
until the status LED of the operation button (7)
flashes.
Briefly press the dimming mode button (2)
repeatedly until the coloured lighting of the
button (2) displays the desired operating mode
(Table 2).
Keep the dimming mode button (2) pressed
until the lighting of the button (2) flashes quickly.
While the button is flashing quickly, the selected
operating mode is set. After that, the operating