Download Print deze pagina

Advertenties

Beschikbare talen

Beschikbare talen

Operating and
assembly instructions
Bedienings- en
montagehandleiding
7534 10 12, 7534 20 12
Switch/blind actuator 2-/1gang
flush-mounted
- 6 A, with 2 binary inputs
- 6 A
Schakel-/jaloezieactor (2-v/1-v)
inbouw
- 6 A met 2 binaire ingangen
- 6 A
8034 10 12, 8034 20 12
Switch/blind actuator 2-/1gang
flush-mounted, system-/easylink
- 6 A, with 2 binary inputs
- 6 A
Schakel-/jaloezieactor (2-v/1-v)
inbouw, , easylink
- 6 A met 2 binaire ingangen
- 6 A
Safety instructions
Electrical equipment may only be installed and
assembled by a qualified electrician in accor-
dance with the relevant installation standards,
guidelines, regulations, directives, safety and
accident prevention regulations of the country.
Failure to comply with these installation in-
structions may result in damage to the device,
fire or other hazards.
Hazard due to electric shock. Disconnect be-
fore working on the device or load. Take into
account all circuit breakers that supply dan-
gerous voltages to the device or load.
Hazard due to electric shock. The device is not
suited for safe disconnection of the mains sup-
ply.
Hazard due to electric shock on the SELV or
PELV installation. Do not connect any loads for
low voltage SELV, PELV or FELV together.
Connect one motor only. If several motors are
connected, motors or device might be destro-
yed.
Use drives with mechanical or electrical final
position switches only. Check final position
switches for correct adjustment. Observe mo-
tor manufacturer's data. The device can be da-
maged.
Observe the motor manufacturer's data regar-
ding change-over time and max. switch-on time
(ED).
These instructions are an integral component
of the product and must be retained by the end
user.
Berker GmbH & Co. KG - Klagebach 38 - 58579 Schalksmühle/Germany - Tel. + 49 (0) 23 55/90 5-0 - Fax + 49 (0) 23 55/90 5-111 - www.berker.com -
1
All manuals and user guides at all-guides.com
Design and layout of the device
z
z
i
(1)
Fig. 1: example device variant with inputs
(1) Illuminated button for manual operation/
programming button
(2) Connection of load(s)
(3) KNX bus connection cable/
connection inputs
Function
System information
This device is a product of KNX system and corre-
sponds to the KNX guidelines. Detailed specialised
knowledge obtained from KNX training courses is
required for understanding. The planning, installa-
tion and commissioning of the device is carried out
with the help of KNX-certified software.
Systemlink commissioning
The function of the device is software-dependent.
The software is to be taken from the product
database. You can find the latest version of the
product database, technical descriptions as well as
z
z
conversion and additional support programmes on
our website.
Easylink commissioning
The function of the device is configuration-depen-
dent. The configuration can also be done using
devices developed specially for simple setting and
start-up.
This type of configuration is only possible with
devices of the easylink system. Easylink stands for
easy, visually supported start-up. Preconfigured
standard functions are assigned to the in/outputs
by means of a service module.
Functional description
The device receives telegrams from sensors or
other controllers via the KNX installation bus and
switches electrical loads with its relay contact.
Correct use
- Switching of electrical loads AC 230 V with
potential-free contact.
- Switching electrically operated motors of
230 V v
230 V AC for blinds, shutters, awnings and
similar hangings.
- Installation into wall box according to
DIN 49073 (use deep box) or junction box
surface-mounted/flush-mounted.
Product characteristics
- Manual activation of the outputs on the device
possible, building site operation.
- Status display of the outputs on the device.
- Scene function.
- Forced position by higher-level controller.
Function in switch operation
- Time switching functions.
(3)
KNX+ /RD
KNX- /BK
In 1 /GN
Com /WH
In 2 /YE
S1
S2
(2)
230 V v
Functions in roller shutter/blind operation
- Position can be started directly.
- Slat position directly controllable.
- Feedback of operating state, shutter position
and slat adjustment.
- 3 Alarms.
Functions of the inputs
- ON/OFF.
- Dimming.
- Up/down.
- Slat angle/Stop.
- Alarm
- Scene.
- Mandatory control.
- Time switching operation.
Information for electricians
Installation and electrical connection
DANGER!
ç
Touching live parts can result in an
electric shock!
An electric shock can be lethal!
Disconnect the connecting cables
before working on the device and
cover all live parts in the area!
Connecting and installing the device
Connecting and installing the device
CAUTION!
ç
Impermissible heating if the load of
the device is too high!
The device and the connected cables
may get damaged in the connection
area!
Do not exceed the maximum current
carrying capacity!
CAUTION!
ç
When connecting the bus/extension
units and mains voltage wires in a
common wall box, the KNX bus cable
might come into contact with the
mains voltage.
The safety of the entire KNX
installation is at risk. Persons could
also get an electric shock even on
remote devices.
Do not place bus/extension units and
mains voltage terminals in a common
terminal compartment. Use a wall box
with a firm partition or separate boxes
(Figure 2).
CAUTION!
ç
Risk of destruction if parallel circuit of
several motors!
Final position switches could fuse
together. Motors, hangings and the
device may be destroyed!
Connect one motor only!
SELV
FELV
KNX+ /RD
KNX- /BK
KNX+ /RD
In 1 /GN
KNX- /BK
Com /WH
In 1 /GN
In 2 /YE
Com /WH
In 2 /YE
S1
S2
S1
S2
230 V AC
230 V v
Figure 2: installation with separate terminal
compartment
KNX+ /RD
KNX- /BK
In 1 /GN
Com /WH
In 2 /YE
S1
S2
6LE000485C

Advertenties

loading

Samenvatting van Inhoud voor Berker 7534 10 12

  • Pagina 1 Function in switch operation compartment - Time switching functions. Berker GmbH & Co. KG - Klagebach 38 - 58579 Schalksmühle/Germany - Tel. + 49 (0) 23 55/90 5-0 - Fax + 49 (0) 23 55/90 5-111 - www.berker.com - 6LE000485C...
  • Pagina 2 The button lights up. Standards EN 50491-3 ; EN 60669-2-1 All manuals and user guides at all-guides.com If the button does not light up, no bus voltage is Dimensions 44 x 43 x 22.5 mm Start-up Start-up Upstream protection circuit breaker 10 A Connection capacity Connection capacity 0.75 mm²…2.5 mm²...
  • Pagina 3 - Statusindicatie van de uitgangen op het apparaat. - Scènefunctie. Berker GmbH & Co. KG - Klagebach 38 - 58579 Schalksmühle/Germany - Tel. + 49 (0) 23 55/90 5-0 - Fax + 49 (0) 23 55/90 5-111 - www.berker.com - 6LE000485C...
  • Pagina 4 Zwitzerland 6LE000485A - 07/2014 6LE000485A - 07/2014 Berker GmbH & Co. KG - Klagebach 38 - 58579 Schalksmü hle/Germany - Tel. + 49 (0) 23 55/90 5-0 - Fax + 49 (0) 23 55/90 5-111 - www.berker.com - 6LE000485C...

Deze handleiding is ook geschikt voor:

7534 20 128034 10 128034 20 12