Operating and assembly instructions
Bedienings- en montagehandleiding
7531 41 14, 7531 ..1 03 7531 90 01
Switch actuator/blind actuator
RMD 10 A
Schakel-/jaloezieactor DIN-rail, 10 A
8031 ..1 03, 8031 90 01
Switch actuator/blind actuator
RMD 10 A, system-/easylink
Schakel-/jaloezieactor DIN-rail, 10 A,
easylink
1
Berker GmbH & Co. KG - Klagebach 38 - 58579 Schalksmühle/Germany - Tel. + 49 (0) 23 55/90 5-0 - Fax + 49 (0) 23 55/90 5-111 - www.berker.com -
Safety instructions
Electrical equipment may only be installed and
assembled by a qualified electrician in accord-
ance with the relevant installation standards,
guidelines, regulations, directives, safety and
z
accident prevention regulations of the country.
i
Failure to comply with these installation in-
structions may result in damage to the device,
fire or other hazards.
Hazard due to electric shock. Disconnect be-
fore working on the device or load. Take into
account all circuit breakers that supply danger-
ous voltages to the device or load.
Hazard due to electric shock. The device is not
suited for safe disconnection of the mains sup-
ply.
Hazard due to electric shock on the SELV/PELV
installation. Not suitable for switching SELV/
PELV voltages.
Connect one motor per output only. If several
motors are connected, motors or device might
be destroyed.
Use drives with mechanical or electrical final
position switches only. Check final position
switches for correct adjustment. Observe mo-
tor manufacturer's data. The device could get
damaged.
Do not connect any three-phase motors. The
device could get damaged.
Observe the motor manufacturer's data regard-
ing change-over time and max. switch-on time
(ED).
These instructions are an integral component
of the product and must be retained by the end
user.
Design and layout of the device
(8)
N
L
auto
(1)
30V DC
-
+
(2)
Fig. 1: Example device variant 8/4gang
(1) Slide switch auto/
(2) KNX bus connection terminal
(3) Connections of loads
(4) Labelling field
(5) Illuminated programming button
(6) Operation button for manual operation per
output with status LED
(7) Connections for switching voltage
(8) Mains power supply connections (only 8gang)
With variants 4/2gang, 6/3gang and
10/5gang the basic design corresponds to the
8/4gang device variant.
z
(7)
1
3
5
7
9
11
13
15
C1
C2
C3
C4
C5
C6
C7
C8
C1
C1
C3
C3
C5
C7
C7
(6)
C2
C2
C4
C4
C6
C8
C8
(4)
(5)
C1
C2
C3
C4
C5
C6
C7
C8
2
4
6
8
10
12
14
16
(3)
Function
System information
This device is a product of KNX system and corre-
sponds to the KNX guidelines. Detailed specialised
knowledge obtained from KNX training courses is
required for comprehension. The planning,
installation and commissioning of the device is
carried out with the help of KNX-certified software.
Systemlink commissioning:
The function of the device is software-depend-
ent. The software is to be taken from the product
database. You can find the latest version of the
product database, technical descriptions as well as
conversion and additional support programmes on
our website.
Easylink commissioning:
The function of the device is configuration-de-
pendent. The configuration can also be done using
devices developed specially for simple setting and
start-up.
This type of configuration is only possible with
devices of the easylink system. Easylink stands for
easy, visually supported start-up. Preconfigured
standard functions are assigned to the in/outputs
by means of a service module.
Functional description
The device receives telegrams from sensors or
other controllers via the KNX installation bus and
switches electrical loads with its independent relay
contacts.
Correct use
- Switch electrical loads of 230 V AC with poten-
tial-free contacts
- Switching electrically operated motors of 230 V
AC for blinds, shutters, awnings and similar
hangings
- Mounting on DIN rail according to DIN EN
60715 in the distribution box
Product characteristics
- manual activation of the outputs on the device
possible, building site operation
- Status display of the outputs on the device
- Scene function
- Forced position by higher-level controller
- Connection of various external conductors pos-
sible
Functions in switch operation:
- Time switching functions
Functions in roller shutter/blind operation:
- Position can be started directly
- Slat position directly controllable
- Feedback of operating state, shutter position
and slat adjustment
- 3 Alarms
Operation
Manual operation switch on/off
With the 8/4gang variants, control of the outputs
is possible even without bus voltage when
mains voltage is connected e.g. for operation at
building sites.
Bus or mains power supply is present.
„ Push switch (1) to position
Manual operation is switched on, the outputs
can be controlled using the operation buttons
(6) independently of each other.
During manual operation, the controller is deac-
tivated via the KNX bus.
Systemlink commissioning:
Depending on the programming, the manual
operation is activated permanently or for a time
.

Advertenties

Inhoudsopgave
loading

Samenvatting van Inhoud voor Berker 7531 1 03 Series

  • Pagina 1 Depending on the programming, the manual operation is activated permanently or for a time Berker GmbH & Co. KG - Klagebach 38 - 58579 Schalksmühle/Germany - Tel. + 49 (0) 23 55/90 5-0 - Fax + 49 (0) 23 55/90 5-111 - www.berker.com -...
  • Pagina 2 period configured via the application software. Connecting loads to be switched CAUTION! ç If the manual operation is blocked via the appli- The output is configured as switching output. Risk of destruction if parallel connec- cation software, no activation takes place. „...
  • Pagina 3 Appendix Variants 8/4gang Warranty Auxiliary voltage 230V~ +10/-15% We reserve the right to make technical and formal Technical data 240V~ +/-6% changes to the product in the interest of technical Supply voltage KNX 21-32V s SELV progress. Energy dissipation Breaking capacity µ...
  • Pagina 4: Opbouw Van Het Apparaat

    Tijdens de handmatige modus is de besturing via de KNX-bus gedeactiveerd. Berker GmbH & Co. KG - Klagebach 38 - 58579 Schalksmühle/Germany - Tel. + 49 (0) 23 55/90 5-0 - Fax + 49 (0) 23 55/90 5-111 - www.berker.com -...
  • Pagina 5: Inbedrijfstelling

    Informatie voor de elektrotechnisch Inbedrijfstelling installateur Systemlink: Fysieke adres en Montage en elektrische aansluiting applicatiesoftware laden De schakelaar (1) staat in de positie auto. GEVAAR! ç „ Busspanning inschakelen. Gevaar voor elektrische schokken bij „ Programmeertoets (5) indrukken. aanraking van onderdelen die onder spanning staan! De toets licht op.
  • Pagina 6: Hulp Bij Problemen

    Bijlage Garantie Varianten 8-/4-voudig Hulpspanning 230V~ +10/-15% Wij behouden ons het recht voor om technische Technische gegevens 240V~ +/-6% en formele wijzigingen aan het product aan te Voedingsspanning KNX 21-32V s SELV brengen, voor zover deze de technische vooruit- Verliesvermogen gang dienen.

Deze handleiding is ook geschikt voor:

8031 1 03 series7531 41 147531 90 018031 90 01

Inhoudsopgave