iNSTallaTiON
Settings
12. Settings
When you enter a four-digit code, additional actual values become
visible, which were hidden beforehand.
12.1 Parameter
P28: Delivered condition OFF
Description
P1
Set room temperature
P2
Intensive ventilation runtime
P3
Bypass mode
P4
Reset filter
P6
Flow rate, stage 0
P7
Flow rate, stage 1
P8
Flow rate, stage 2
P9
Flow rate, stage 3
P14 Supply air flow rate offset
P15 Humidity protection interval
P16 Start-up time for humidity measurement
P17 Extract air humidity limit
P18 Frost protection temperature
P19 Filter change interval
P22 Enable preheater
P23 Frost protection mode
P24 Bypass enable temperature
P25 Bypass blocking temperature
P26 Bypass hysteresis
P27 Temperature differential for enabling the bypass
P28 Enable fan
P29 Appliance type
P30 Temperature for enabling frost protection
P31 Enabling of humidity-dependent flow rate control A1
P32 Enable outdoor air condensate prevention
P33 Temperature offset for condensate prevention
P35 Bypass function cooling/heating
P70 Delete fault list
P80 Day
P81 Time
P82 Level of lighting
P83 Mode of backlighting
P84 Illumination duration
P85 Lower standard display
www.stiebel-eltron.com
All manuals and user guides at all-guides.com
VRC-W 400
Code Unit
min. max. Options
A0
°C
5
28
A0
Min.
1
240
A0
A0
A1
m³/h
40
150
A1
m³/h
60
300
A1
m³/h
60
400
A1
m³/h
60
400
A1
-100
100
A1
h
1
24
A1
min
5
15
A1
%
5
95
A1
°C
-10.0 10.0
A1
d
1
365
A1
A1
A1
°C
5.0
15.0
A1
°C
5.0
15.0
A1
K
0.0
5.0
A1
°C
0.0
5.0
A0
A1
A2
°C
-10.0 10.0
A2
A2
K
-5.0
5.0
A2
A1
A0
1
7
A0
00:00 23:59
A0
2
10
A0
A0
s
10
500
A0
VRC-W 400 E
Stand-
min. max. Options
ard
20
5
30
1
0 | 1 | 2 | 3
2
0 | 1
-
60
40
140
60
200
60
260
60
0
-100
1
1
5
5
65
5
4.0
-10.0 10.0
90
1
0 | 1
1
0 | 2
2
10.0
5.0
8.0
5.0
2.0
0.0
2.0
0.0
On | OFF
On
9
-3.0
-10.0 10.0
0 | 1
0
0 | 1
0
0.0
-5.0
1 | 2 | 3
1
0 | 1
-
1
00:00 23:59
10
2
Auto | On | OFF
Auto
60
10
OFF | Time | Set room
OFF
temperature | Extract
air temp. | Extract air
humidity
Stand-
ard
28
20
240
30
0 | 1 | 2 | 3
2
0 | 1
-
150
60
300
140
400
200
400
260
100
0
24
1
15
5
95
65
4.0
365
90
0 | 1
1
0 | 2
2
15.0
10.0
15.0
8.0
5.0
2.0
5.0
2.0
On | OFF
On
10
-3.0
0 | 1
1
0 | 1
0
5.0
0.0
1 | 2 | 3
1
0 | 1
-
7
10
10
Auto | On | OFF
Auto
500
60
OFF | Time | Set room
OFF
temperature | Extract
air temp. | Extract air
humidity
VRC-W 400 (E) |
17