Elpro 7 RP
GB
Preliminary notes to Learning Mode:
- Make sure that the gate is closed
- Make sure that the gate stops in the respective open and closed gate
positions are firmly fixed to the ground
1°
st Operation
1
:
Cut off power supply to Elpro 7RP by removing the
2A 24V Low Voltage white Fuse, which is on the
right upper side of the PCB
2°
nd Operation:
2
Hold the button "P" pressed and re-power the PCB by
inserting the 24V Low Voltage Fuse back into its holder.
3°
L7
rd Operation:
3
When the Led L7 illum inates, release button "P" : Led L7 will flash
5 tim es and the flashing lam p will illum inate: the program "learning
working tim es" has been entered.
IMPORTANT: at this stage two options are allowed to go on with
!
setting ie. learning the required operating times: by the "P" button or
by rem ote control. The last option allows the installation agent to
have direct visual control of the operation being perform ed
by the gates.
4°
th Operation:
4
A pulse to open starts M1 motor
( the first gate starts opening )
The time passing from 4th to 5th operations is stored by the system
!
as the Gate Delay Time in Open Cycle , with the options in service
(Dip No.6 = ON) or out of service (Dip No. 6= OFF, the time is stored
but no delay will occur).
5°
th Operation:
5
A pulse to open starts M2 motor
( second gate starts opening )
6°
th Operation:
6
A pulse stops M1 motor
( first gate wide open on open gate stop )
Drwg. No. 4153
L7
L7
L7
M2
M2
M2
7°
th Operation:
7
A pulse stops M2 motor
( second gate wide open on open gate stop )
The time passing from 7th to 8th operation is stored by the system
!
as " Dwell Time ", in service on AUTOMATIC MODE (Dip No.3= ON)
or out of service (Dip No.3= OFF, dwell time still in the system
memory but not applicable ).
8°
th Operation:
8
A Pulse to close starts M2 motor
( M2 gate starts closing )
The time between the 8
!
as " Gate Delay Time on Closing Cycle"
9°
th Operation:
9
A pulse to close starts M1 motor
( M1 gate starts closing )
10°
M1
th Operation
10
:
A pulse stops M2 motor ( M2 gate on closed gate position )
In order to ensure that the gate is securely held in stop position, it is advised
to pulse the actuator ie. gate to stop approx. 3-4 seconds after the gate
has reached the end of the permitted stroke on the closed gate stop
position.
11°
M1
th Operation:
11
A pulse stops M1 motor ( M1 gate on closed gate position )
In order to ensure that the gate is securely held in stop position, it is advised
to pulse the actuator ie. gate to stop approx. 3-4 seconds after the gate
has reached the end of the permitted stroke on the closed gate stop
position.
th
The 11
operation concludes the procedure for the control panel
M1
to learn the required working times.
After the learning procedure it is possible to set the operating modes
either ON/OFF as required by means the Dip-switches on the PCB
M2
M2
th
th
and 9
operations is stored by the system
M2
M2
M1
M2
M1
M1
M1
M1
the gate opener
Made in Italy
pag. 5