ATTENTION
Please read the following instructions carefully to ensure that mounting operation will be carried out correctly. These instructions
should be properly preserved for future reference.
CAUTION
1. The product must be installed by qualified technicians. The power supply must be cut before installation.
2. The installation wiring must be 2x 1.0mm² at least and wired in accordance with the latest IEE electrical regulations or the national requirements.
3. Cut the power supply before replacing battery.
4. Do not touch the electronic circuit and its components.
5. When fixture is unable to maintain the 1 hour duration under battery operation, then the battery must be replaced.
6. Contact an authorised technical service center for the replacement of the battery and use only original manufacturer spare parts for any other
repairs.
7. Code for identification of battery production date: ex.1610 --- 2016, week10.
8. Do not touch the LEDs while installing or maintaining.
9. The LED light source of the lamp cannot be replaced. The complete product must be replaced if the light source is defect.
10. The charge of the battery will decrease by self-discharge if not connected to mains supply. Prolonged periods without voltage can damage the
battery. Battery warranty claims, as a result of such abuse, are specifically EXCLUDED from warranty terms.
11. On many building sites, power circuits may be cut off in an uncontrolled and repetitive basis during construction. As a result, any unit on these
circuits, will have their batteries discharged or 'cycled' . Excessive battery cycling will reduce through-life performance and may lead to premature
battery failure. Battery warranty claims, as a result of such abuse, are specifically EXCLUDED from warranty terms.
TECHNICAL DATA
Supply voltage: AC 220-240V 50/60Hz
Light source: LED SMD2835
Batteries: Ni-Cd
Duration: 1h
Operating temperature: -20°C - +50°C
Electrical safety class: Class II
TECHNICAL INFORMATION
Input
Art.no.
LED type
power
4001002x
SMD2835
7.5W
4001003x
SMD2835
8.5W
MICROWAVE SENSOR - DESCRIPTION
Detection zone max. (d x h): 14m x 6m
Detection sensitivity: 25% - 100%, adjustable
Hold time: 5sec - 30min, adjustable
Daylight 1: 5 - 15Lux, adjustable or disable
Daylight 2: 35 - 150Lux, adjustable or disable
(with daylight priority)
Hold time: 5 - 30sec - 1 - 5 -15 - 30min (adjustable)
Hold time orientation lighting:
0 - 10 - 20 - 30 - 60 - ∞ min (adjustable)
Mounting height: 6m max.
Motion detection: 0.5 ~ 3m/s
Detection angle: 150° (wall installation),
360° (ceiling installation)
Lumen
Lumen Emer-
switchable
gency mode
600Lm / 300Lm
200Lm
600Lm / 300Lm
200Lm
Wall mounting pattern (Unit: m)
Suggested installation height: 1 - 1.8m
www.prolumia.eu
Mode of
Sensor
Duration
operation
(Non) maintained
-
1h
(switchable)
(Non) maintained
Yes
1h
(switchable)
Battery
Ni-CD 2/3AA450mAhHT 7.2V
Ni-CD 2/3AA450mAhHT 7.2V
Ceiling mounting pattern (Unit: m)
Suggested installation height: 2.5 - 6m
9