Location
The Centaur Charger must be installed in a dry, well-ventilated
area.
Too high an ambient temperature has the consequence of lower
output, shorter life or a complete shutdown of the Centaur
Charger.
The Centaur Charger is suitable for floor and wall mounting.
However, for optimum cooling, a vertical position is recommended.
The cables between the Centaur Charger and the battery must be
kept as short as possible to minimize cable losses. Input/output
connections refer to Figure 1.
Required tools and cables
• M6 Socket driver.
• Crosshead screwdriver no. 2 Phillips.
• Battery cables: minimum cable cross-section
Model
Length 0 - 6 m
12/20
10 mm²
24/16
AWG 7
12/30
16 mm²
12/40
AWG 5
24/30
24/40
12/50
25 mm²
12/60
AWG 3
24/60
12/80
35 mm²
12/100
AWG 2
24/80
24/100
12/200
50 mm²
AWG 0
7