Beschikbare talen

Routine duration
If there is no temperature flushing within
the configured interval, the water ex-
change is guaranteed through the „Routine
duration" operating mode. To accomplish
Routine volume
If there is no temperature flushing within
the configured interval, the water ex-
change is guaranteed through the „Routine
volume" operating mode. To accomplish
Configuration of a Hygiene flushing box
© www.kemper-olpe.de – 08.2021 / 410068602009-00 – 81 / 128
that, the decisive interval (max. 168 h) and
the duration of the water exchange can be
stored in the „Routine duration" operating
mode.
this, the decisive interval (max. 168 h), the
volume and the maximum flushing time of
the water exchange can be assigned to the
„Routine volume" operating mode.
Save settings
For the new parameters of the input box
to become effective, the settings must be
saved by clicking
SAVE
Select time flushing
After a line has been added using
LINE, the line type is selected. The „Time
flushing" line type is selected from the
drop-down list.
CONFIGURATION.
ADD