Download Inhoudsopgave Inhoud Print deze pagina

Installation; Positioning - Saey QURVE Installatie- En Gebruiksaanwijzing

Inhoudsopgave

Advertenties

Beschikbare talen

Beschikbare talen

7 I
NSTALLATION
All local regulations, including those referring to national and European standards need to be complied with
when installing the appliance.
Only an appliance connected by a qualified installer guarantees compliance with legislation on construction
and fire prevention. This is certainly required for safe and proper use of the stove.

7.1 Positioning

The appliance shall be erected on floors with an adequate loadbearing capacity (see technical data). If an
existing construction doesn't meet this prerequisite, suitable measures shall be taken to achieve it.
Adjust if necessary the feet of the appliance to position it at level.
If the stove is installed on an inflammable floor, then place a fireproof plate underneath the appliance. Make
sure to respect the following safety clearance distances from combustible materials:
Front
80 cm
Rear
40 cm for combustible wall
10 cm for non-combustible wall
Sidewards 80 cm
7.2 Combustion air
The required oxygen for the fire is supplied through the lower backside of the stove.
An optimal combustion requires sufficient fresh air. A lack of oxygen may result in incomplete combustion
and reversing flue gases.
ATTENTION!
Extractor fans when operating in the same room or space as the appliance may cause problems.
Additional combustion air can be supplied by placing an air inlet grill as close as possible to the appliance.
Air inlet grills must be positioned so that they are not liable to blockage.
Fresh air supply enables the additional deliverable outdoor air connection to come into force. Remove the
rupture disc on the back of the coat. Place and install the outdoor air connection under the fireplace by
using non-combustible drainage materials with a diameter of 80 mm.
31

Advertenties

Inhoudsopgave
loading

Inhoudsopgave