Instructies voor gebruik en onderhoud – v4.2.2
FUNCTIONALITEIT
ALS BEDRIJFSMODUS CPS
REACTIESNELHEID VAN
INSTELLING VAN DE REACTIESNELHEID VAN HET ALGORITME CPS.
HET ALGORITME CPS
DE WAARDE 10 (STANDAARDWAARDE) CORRESPONDEERT MET
DM 4.0.0 | TAC-
DE HOOGSTE REACTIESNELHEID. ELKE STAP VAN -1 CORRES-
TOUCH:2.44
PONDEERT MET EEN VERDUBBELING VAN DE REACTIETIJD (10=T,
9=2XT, 8=4XT, ...).
WIJ ADVISEREN DEZE WAARDE UITSLUITEND TE WIJZIGEN VOOR
TOEPASSINGEN VOOR HET HANDHAVEN VAN EEN CONSTANTE DRUK
IN EEN RUIMTE (EN NIET IN EEN BUIS).
REACTIESNELHEID VAN
INSTELLING VAN DE LOGICA VAN DE MODUS CPS:
HET ALGORITME CPS
NEGATIEVE LOGICA:
DM 4.0.0 | TAC-
- DE LUCHTSTROOM NEEMT AF ALS HET SIGNAAL GEMETEN OP K2
TOUCH:2.44
> DE INSTELWAARDE
- DE LUCHTSTROOM NEEMT TOE ALS HET SIGNAAL GEMETEN OP
K2 < DE INSTELWAARDE
POSITIEVE LOGICA:
- DE LUCHTSTROOM NEEMT TOE ALS HET SIGNAAL GEMETEN OP
K2 > DE INSTELWAARDE
- DE LUCHTSTROOM NEEMT AF ALS HET SIGNAAL GEMETEN OP K2
< DE INSTELWAARDE
ALS BEDRIJFSMODUS CA OF LS
STOPZETTING VAN DE
MOGELIJKHEID OM DE VENTILATOREN AUTOMATISCH STOP TE
VENTILATOREN IN GEVAL
ZETTEN IN GEVAL VAN EEN DRUKALARM (NA ANNULERING VAN HET
VAN EEN DRUKALARM
ALARM MOET U OP RESET DRUKKEN OM DEZE TE HERSTARTEN).
DM 4.0.0 | TAC-
TOUCH:2.44
54
BESCHRIJVING
Dit document is een overzicht van de technische specificaties. Raadpleeg onze selectiesoftware voor gedetailleerde en actuele informatie.
TAC5 DM
STAP
TEKST OP HET
SCHERM
9
SNELHEID CPS? 10 CONSTANTE DRUK/REACTIESNELHEID
10
LOGICA? NEGATIEF
CONSTANTE DRUK/LOGICA
11/12
STOP VENT ALS
STOPZETTING ALS DRUKALARM
ALARM PA? N
TAC5 DM + TACTOUCH