Download Inhoudsopgave Inhoud Print deze pagina

Cooling Capacity Tables; Capaciteitentabellen Voor Koeling - Daikin Altherma 3 GEO EGSAH06D 9W Series Handleiding

Verberg thumbnails Zie ook voor Altherma 3 GEO EGSAH06D 9W Series:
Inhoudsopgave

Advertenties

4
Capacity tables
4 - 2

Cooling Capacity Tables

EGSAX-D9W
EGSAX-D9WG
4
LWC [°C]
EBT [°C]
-5
0
5
10
15
20
25
30
-5
0
5
10
15
20
25
30
Legend
LWC: Leaving water temperature [°C]
EBT: Entering brine temperature [°C]
CC:
Cooling capacity at maximum operating frequency, measured according to ·EN14511:2018·.
PI:
Power input at maximum operating frequency (including the controller and the pumps), measured according to
·EN14511:2018·.
Conditions
Cooling capacity
The capacity is according to ·EN14511:2018· and valid for chilled water range Dt = ·3~8·°C
Capacity values may not be extrapolated below 7°C leaving water temperature.
24
7
13
CC [kW] PI [kW] CC [kW] PI [kW] CC [kW] PI [kW] CC [kW] PI [kW] CC [kW] PI [kW]
8,12
0,57
11,27
1,28
11,76
1,43
11,94
1,50
11,85
1,61
12,61
1,65
11,17
1,68
12,10
1,73
10,49
1,76
11,59
1,81
9,82
1,84
11,08
1,89
9,14
1,92
10,57
1,98
8,12
0,57
9,73
1,00
10,04
1,11
10,31
1,16
10,13
1,22
10,90
1,25
9,80
1,38
10,74
1,42
9,46
1,55
10,57
1,59
9,13
1,71
10,41
1,76
8,79
1,87
10,24
1,93
Maximum cooling capacity
15
18
8,12
0,57
8,12
0,57
11,27
1,27
11,28
1,25
12,00
1,50
12,10
1,50
12,73
1,65
12,92
1,66
12,35
1,72
12,74
1,71
11,97
1,79
12,56
1,76
11,59
1,86
12,37
1,81
11,21
1,93
12,19
1,86
8,12
0,57
8,12
0,57
9,73
1,00
9,73
0,99
10,40
1,15
10,52
1,14
11,06
1,24
11,30
1,23
11,04
1,40
11,49
1,38
11,01
1,57
11,67
1,54
10,99
1,73
11,86
1,69
10,96
1,90
12,04
1,84
Daikin Altherma ground source heat pump
22
8,12
0,57
11,29
1,24
12,24
1,49
13,18
1,66
13,25
1,69
13,33
1,72
13,41
1,74
13,49
1,77
8,12
0,57
9,73
0,97
10,68
1,12
11,62
1,22
12,09
1,36
12,56
1,49
13,02
1,63
13,49
1,77
3D124144
EGSAH-D9W / EGSAX-D9W / EGSAX-D9WG

Advertenties

Inhoudsopgave
loading

Inhoudsopgave