Manual operation

In manual mode, the temperature is controlled in accordance with
the current temperature set via the push-buttons (E and F). The tem-
perature remains activated until the next manual change. To activate
the manual mode, please proceed as follows:
Select "Manu" via the plus and minus buttons (E and F) in the
menu.
Confirm with the menu button.
To confirm, the symbol flashes twice and the device changes back
to manual mode.
6.3

Offset temperature

As the temperature is measured on the radiator thermostat, the tem-
perature distribution can vary throughout a room. To adjust this, a
temperature offset of ±3.5 °C can be set. If a nominal temperature
of e.g. 20 °C is set but the room presents with only 18 °C, an offset
of -2.0 °C needs to be set. An offset temperature of 0.0° is set in the
factory settings. To adjust the offset temperature, please proceed as
follows:
Select "Offset" via the plus and minus buttons (E and F) in the
menu.
Confirm with the menu button.
Select the desired offset temperature using the plus or minus
button and confirm with the menu button.
To confirm, the temperature flashes twice and the device changes
back to the standard display.
Configuration menu of the radiator thermostat