6. Commissioning

The activities described in this section must only
be executed by a qualified electrician.
6.1

Switching on the device

T
DANGER
Electric shock hazard when devices are damaged
If a damaged device is used people can be seriously inju-
red or killed through an electric shock.
f Do not use the device if it is damaged.
f Mark the damaged device to ensure that no one conti-
nues using it.
f Eliminate the damage immediately.
f Take the device out of service if necessary.
Precondition:
„ Device is installed correctly.
„ Device is in a proper condition.
„ There is no residual current device sensitive to pulse
current (type A) in the upstream electrical installation.
„ All protective devices (e.g. residual current devices, line
circuit breakers and contactors) function correctly and
are switched on.
„ During the initial setting-up process, the device was
inspected in accordance with IEC 60364-6 and the
applicable national regulations (e.g. in Germany: DIN
VDE 0100-600).
Î "6.2 Checking the device"
f Switch the power supply on.
9
The LED on the power supply unit will light.

6.2 Checking the device

Test according to IEC 60364-6 and the applicable nation-
al regulations (e.g. in Germany DIN VDE 0100-600)
Prior to the initial setting-up process, carry out an inspec-
tion of the charging station in accordance with
IEC 60364-6 and the applicable national regulations (e.g. in
Germany DIN VDE 0100-600). The test can be carried out
in connection with the MENNEKES test box and a standard-
compliant test equipment. The MENNEKES test box simu-
lates vehicle communication. Test boxes are available as
accessories from MENNEKES.
f Perform a standard test before the device release.

Operating instructions of the test box.

6.3 Final procedures at charging column

T
ATTENTION
Device damage due to crushed components or cables
If components or cables are crushed when closing the
device, damage and malfunctions can occur.
f When closing the device ensure that components or
cables are not crushed.
f If necessary fix components or cables in place.
After installation and commissioning, you must carry out
the following steps:
f Check the firm seating of water discharge hoses.
f Insert the front plate in the basic enclosure and inter-
lock the front plate with the turning lever.
f Remove the key from the cylinder lock and check the
interlock.
f Close the cover plate and interlock cover plate and
cover lock on the back of the charging column.
f Remove any protective film from the enclosure of the
charging station.
9
Start-up is now complete and the charging column is
operational.
MENNEKES recommends using pedestal filler for
protection against humidity and insects.