Download Inhoudsopgave Inhoud Print deze pagina

Inhoudsopgave; Principle Of Operation; Technical Data - TTM NoXygen F650 Installatie-Instructie

Ontgasser
Inhoudsopgave

Advertenties

Beschikbare talen

Beschikbare talen

TTM NoXygen
EN
Installation, operating and maintenance instructions
Table of Content
General
Principle of Operation ................................................... 2
Technical Data .............................................................. 2
General Safety Instructions .......................................... 3
.............................................................. 4
Pipe connection .......................................................... 4
Electrical Connection .................................................. 4
..................................................................... 6
Factory Reset ............................................................... 6
Alarm list ....................................................................... 6
................................................ 6
.......................................................... 7
............................................... 9
....................................................11

Technical data

Art.no .................................................... 519171
System pressure at the connection point,
max.: .....................................................+5.0 bar
Allowable operational temperature: ........-10 - +70 °C
Ambient temperature: ............................0 - +40 °C
Allowable fluids:
Pressure classification: ..........................PN10
Capacity, degassed fluid: .......................min. 125 l/h
Connection dimension: ..........................DN15
Electrical data: .......................................1~230 V, 50 Hz, plug
Internal fuse: .........................................10 A
Nominal power: .....................................0.75 kW
Nominal current: ....................................5,0 A
Protective class: ....................................IP44
Energy usage: .......................................37 kWh/year **
Communication protocol: ......................Modbus RTU (RS485)
Sound level: ...........................................61 dB
Weight: ..................................................30 kg
*) When degassing ethanol, make sure the room is well ventilated.
) Operation with 30 days of fast degassing gives a
**
energy consumption of 102 kWh in the first year.
2
F650
®
...................... 5
..........................................10
Water and deionised water
Propylene/ethylene glycol max. 50 vol%
Ethanol* less than 30 vol%
Salt solution Temper T10, T20, T30, T40
Kilfrost GEO max. 35 vol %
Calcium chloride max 25 %
Slöjdaregatan 1 | 393 66 Kalmar | Sweden | Tel. + 46 480-41 77 40 | info@ttmenergi.se | www.ttmenergi.se
Upon delivery
Instructions: Immediately upon receiving, check to ensure
that the delivery is complete and that nothing
is damaged.
Report any transport damage immediately.

Principle of Operation

A
B
C
290
180
654
Width:
Height:
Depth:
For latest updates visit www.ttmenergi.se.
2024-06
D
A. Main pipe (return)
B. Inlet with shut-off valve
C. Treatment chamber
D. Return with shut-off valve
140
1/2" int. thread
253
654 mm
960 mm
253 mm
TTM Energiprodukter AB