Download Inhoudsopgave Inhoud Print deze pagina

Advanced Menu Overview - Zehnder ComfoSense C55 Handleiding

Verberg thumbnails Zie ook voor ComfoSense C55:
Inhoudsopgave

Advertenties

Beschikbare talen
  • NL

Beschikbare talen

  • DUTCH, pagina 1
7

Advanced menu overview

Menu item
ADVANCED SETTINGS
SENSOR
VENTILATION
TEMPERATURE
PROFILE
TEMPERATURE UNIT
SEASON DETECTION
RF PAIRING
RESET TO INSTALLER
DEFAULTS
Function
Demand control ventilation based on the built-in sensors within
the HRU. The following functions can be set:
PASSIVE TEMPERATURE
ACTIVE TEMPERATURE
COMFORT HUMIDITY
PROTECTION HUMIDITY
■ ON: to set the selected function to be permanently active.
■ AUTO ONLY: to set the unit to only activate the selected
function when it is in AUTO mode.
■ OFF: to set the unit to never activate the selected function.
See HRU manual.
To set the settings of the temperature profile.
■ ADAPTIVE: The desired indoor temperature to which the unit will
adjust the heat recovery control varies with the outdoor climate
(adaptive comfort technology). The set temperature can be
increased or decreased with 1.5°C from the average setting by
selecting the WARM or COOL temperature profile; (default setting).
■ FIXED: The desired indoor temperature to which the unit will
adjust the heat recovery control is fixed and does not depend on
the outdoor climate. The set temperatures can be changed in
FIXED PRESETS for each temperature profile.
■ WARM: set the temperature for the temperature profile
mode WARM in FIXED mode; (Default = 24°C or 76°F).
■ NORMAL: set the temperature for the temperature profile
mode NORMAL in FIXED mode; (Default = 20°C or 68°F).
■ COOL: set the temperature for the temperature profile mode
COOL in FIXED mode. (Default = 18°C or 64°F).
Set the temperature display to °C or °F.
To adjust the season detection for bypass.
■ HEAT UNTIL RMOT: To set a RMOT limit to prevent the HRU
from counteracting the effect of the central heating system.
■ COOL ABOVE RMOT: To set a RMOT limit to prevent the
HRU from counteracting the effect of the air conditioning.
To connect an RF device.
■ START: Starts the RF pairing procedure. When multiple
ComfoSense C devices are used, one should be chosen to
act as RF-bridge to connect the RF sensors to.
■ DEL: Deletes the currently paired RF devices.
■ RESET: All settings mentioned in this document except
BASIC SETTINGS, RF PAIRING, RF ON/OFF will be reset to
their default values.
31

Advertenties

Inhoudsopgave
loading

Deze handleiding is ook geschikt voor:

Comfosense c67Comfosense cch

Inhoudsopgave