Download Inhoudsopgave Inhoud Print deze pagina

Jbus/Modbus Protocol; Jbus/Modbus Table - socomec COUNTIS E43 Gebruiksaanwijzing

Wattuurmeter via tc 5a met jbus/modbus-communicatie
Inhoudsopgave

Advertenties

14
PRéSENTATIoN
INTRoDuCTIoN - DARSTElluNG - PRESENTAzIoNE - PRESENTATIE - PRESENTACIóN - APRESENTAção
JBuS/modBuS communication
JBuS/modBuS mEdia
GB
In a standard configuration, one RS485
connection enables 32 UL* to be connected to a PC
or PLC over 1200 metres using the JBUS/MODBUS®
protocol.
* 1 UL = 2 Countis E43.
Recommendations:
An LIYCY type shielded twisted pair must be used. In
an environment with interference or on a long network
with a large number of COUNTIS, we recommend
using a shielded twisted pair with general LIYCY-CY
shielding.
If the distance is greater than 1200 m and /or there
are more than 64 COUNTIS, a repeater (1 channel) or
a spark arrester (2 channels) must be connected to
enable the connection of additional COUNTIS with
communication interface over more than 1200 m.
For more information on the connection procedure,
refer to the technical bulletin available on the web
site: www.socomec.com
COUNTIS E43 - Ref.: 537 885 A
important:
It is essential to connect a resistance of 120 Ohms
to the 2 ends of the connection; this can be found in
the product packaging. Other solutions are available
(modem, fibre optic, etc.); please ask for details.

JBuS/modBuS protocol

The JBUS/MODBUS protocol operates on a master/slave
structure:
• Reading (Function 3),
• Writing (Function 6 or 16), broadcast option at
address 0.
The communication method is RTU (Remote Terminal
Unit) with hexadecimal characters comprising a
minimum of 8 bits.

JBuS/modBuS table

File Ref: 538461
Can be downloaded from the web site:
www.socomec.com
R=120Ω
R=120Ω
R=120Ω
R=120Ω
RS485 COUNTIS
R=120Ω
R=120Ω
R=120Ω

Advertenties

Inhoudsopgave
loading

Inhoudsopgave