I. Installation
Installation must be carried out by qualified service
personnel in accordance with the Installation Manual
supplied with this icemaker. The owner/manager should
also be aware of the installation-related information
below.
WARNING
1. This icemaker must be installed in accordance with
applicable national, state, and local regulations.
2. CHOKING HAZARD: Installer must ensure all
components, fasteners, and thumbscrews are
securely in place after installation. Make sure that no
components, fasteners, or thumbscrews have fallen
into the ice storage bin.
A. Location
NOTICE
1. This icemaker is not intended for outdoor use.
Normal operating ambient temperature should
be within 45°F to 100°F (7°C to 38°C); Normal
operating water temperature should be within
45°F to 90°F (7°C to 32°C). Operation of the
icemaker, for extended periods, outside of these
normal temperature ranges may affect icemaker
performance.
2. This icemaker will not work at sub-freezing
temperatures. To prevent damage to the water
supply line, have a qualified service technician drain
the icemaker if the air temperature is going to go
below 32°F (0°C).
3. Do not place anything in front of the louver(s)
(air-cooled models).
B. Electrical Connection
WARNING
1. Electrical connection must meet national, state, and
local electrical code requirements. Failure to meet
these code requirements could result in death,
electric shock, serious injury, fire, or severe damage
to equipment.
2. This unit requires an independent power supply of
proper capacity. See the nameplate for electrical
specifications. Failure to use a properly sized
breaker or fuse can result in a tripped breaker,
blown fuses, or damage to existing wiring. This
could lead to heat generation or fire.
3. THIS UNIT MUST BE GROUNDED (EARTHED).
Failure to properly ground (earth) this unit could
result in death or serious injury.
• Usually an electrical permit and services of a licensed
electrician are required.
• If a power cord and/or a plug should need to be fitted/
replaced, it should only be done by a qualified service
technician.
• Factory fitted power cords are coloured in accordance with
the following code:
Green and Yellow = Ground (Earth)
Blue = Neutral
Brown = Line
For the UK and the Republic of Ireland Only
For Models with a Plug:
• The non-rewirable plug must never be used without a fuse
cover being fitted.
• The correct replacement for the detachable fuse cover
is identifiable from the manufacturer's reference number
stamped on the plug.
• Supply of replacement fuse covers can be obtained from
Hoshizaki Parts/Service Centres.
• Fuses should be rated at 13A and approved to BS 1362.
C. Water Supply and Drain Connections
1. Water supply and drain connections must be
installed in accordance with applicable national,
state, and local regulations.
2. The icemaker water supply must be potable water.
3. Normal operating water temperature should be
within 45°F to 90°F (7°C to 32°C). Operation of
the icemaker, for extended periods, outside of this
normal temperature range may affect icemaker
performance.
4. Water supply pressure should be a minimum of
10 PSIG (0.7 bar) and a maximum of 113 PSIG
(7.8 bar). If the pressure exceeds 113 PSIG (7.8 bar),
the use of a pressure reducing valve is required.
DO NOT throttle back the supply tap.
5. To prevent damage to equipment, do not operate
the icemaker when the water supply is off, or if the
pressure is below 10 PSIG (0.7 bar). Do not run the
icemaker until the proper water pressure is reached.
• A plumbing permit and services of a licensed plumber may
be required in some areas.
• External filters, strainers, or softeners may be required
depending on water quality. Contact your local Hoshizaki
distributor for recommendations.
• Drain lines should not be piped directly to the sewer
system. An air gap of a minimum of 2 vertical inches
(5 cm) should be between the end of the drain pipes from
the icemaker and condensation drain and ice storage bin
and the floor drain.
3
WARNING