1.1 General Disclaimer
•
The information in this quick installation guide is subject to change due to product updates or other reasons. This
guide cannot replace the product labels or the safety precautions in the user manual unless otherwise specified. All
descriptions here are for guidance only.
•
Before installations, read through the quick installation guide. For additional information, please see the user
manual.
•
All operations should be performed by trained and knowledgeable technicians who are
familiar with local standards and safety regulations.
•
Check the deliverables for correct model, complete contents, and intact appearance. Contact the manufacturer if any
damage is found or any component is missing.
•
Use insulating tools and wear personal protective equipment when operating the equipment to ensure personal
safety. Wear anti-static gloves, clothes, and wrist strip when touching electronic components to protect the inverter
from damage. The manufacturer shall not be liable for any damage caused by static electricity.
•
Strictly follow the installation, operation, and configuration instructions in this guide and user manual. The
manufacturer shall not be liable for equipment damage or personal injury if you do not follow the instructions. For
more warranty details, please visit
1.2 Safety Disclaimer
Warning
DC Side:
1. Ensure the component frames and the bracket system are securely grounded.
2. Connect the DC cables using the delivered PV connectors. The manufacturer shall not be liable for equipment
damage if other connectors are used.
3. Ensure the DC cables are connected tightly, securely, and correctly. Inappropriate wiring may cause poor
contacts or high impedances, and damage the inverter.
4. Measure the DC cable using the multimeter to avoid reverse polarity connection. Also, the voltage should be under
the max DC input voltage. The manufacturer shall not be liable for the damage caused by reverse connection and
extremely high voltage.
5. The PV modules used with the inverter must have an IEC61730 class A rating.
AC Side:
1. The voltage and frequency at the connecting point should meet the on-grid requirements.
2. Additional protective devices like circuit breakers or fuses are recommended on the AC side. Specification of the
protective device should be at least 1.25 times the rated AC output rated current.
3. PE cable of the inverter must be connected firmly. The resistance between the neutral wire and the earth cable is
less than 10Ω.
4. You are recommended to use copper cables as AC output cables. If you prefer aluminum
cables, remember to use copper to aluminum adapter terminals.