Alarm reports :
-
2 dry contacts (open when faulty) 1A@24Vdc, 0.5A@120Vac :
mains fault or rectifier fault
o
battery low voltage fault
o
-
Indicated by a LED on the front panel
•
Protection :
-
Fuses on electronic board: see table
It is mandatory to install batteries after fixing the base of the cabinets to the wall (wall mounting
Warning!
with 3 or 4 points).
Connections
run cables through the inputs / outputs provided in the cabinet
-
cable section, mains, load, battery alarm reports:
-
0.2 to 2.5 mm² (12V 2A - 12V 5A – 24V 1A - 24V 2.5A)
o
length to be stripped: 7mm
-
the bare parts of the cables must be crimped before being wired to the terminals of the product.
-
Warning!
For compliance with EN 50131-6 Grade 2, it is mandatory to wire cover opening contact.
•
Commissioning and operation instructions can be downloaded from www.slat.com.
•
No equipment may be returned without prior issuance of an RMA number.
•
For additional technical assistance, or to request and RMA number,
contact the SLAT hotline on +33 (0) 4 78 66 63 70
•
Product warranty: 3 years, cf. our general sales terms
Installation
Commissioning and Technical Support
Code :
180150012Da
- NDU :
NOT150004Da - Edition : 09/24
4