Installa� on led indicator lamp including test bu� on func� on
1. Determine the loca� on of the indicator lamp and make a hole of Ø20mm.
2. Remove the white edge of the indicator lamp with a small screwdriver and also remove the second
underlying white rim.
3. Insert the black indicator lamp into the drilled hole and replace the white rings.
4. Now place the assembly back into the drilled hole.
Func� on of the indicator
LED INDICATION
STATUS
Steady green
Standby, System OK
Flashing green briefl y (0.25 sec.)
Func� on test
Flashing green long (1 sec.)
Con� nuous test
Con� nuous red
Lamp failure
Red fl ashing short (0.25 sec.)
Ba� ery failure
Red fl ashing long (1 sec.)
Ba� ery failure
Green and red OFF
Ba� ery opera� on
Specifi ca� ons
Dimensions
300 x 130 x 47mm
Input Voltage
220-240Vac, 50/60Hz
Output Voltage
20-60Vdc
Ba� ery type
LiFePO4 3,000mAH 3.2Vdc
Charging � me
<24 hours
Tes� ng (automa� c/manual)
Automa� c tes� ng
• Func� on test: every 7 days a short (5 seconds) func� on test is performed to check the
emergency ligh� ng module, the ba� ery and the connected LED lights.
• Ini� al dura� on test: this is performed 24 hours a� er installa� on.
• Semi-annual endurance test: this is performed a� er every 180-182 days.
Manual tes� ng
• Test bu� on short press starts a short func� on test that will last 5 seconds.
• Test bu� on long press (>10 seconds) resets the built-in (test) � mer for
automa� c tes� ng.
• A� er installa� on, the green LED light will blink for up to 6 days before being permanently lit. This is a sign that the
endurance test has been successful
DESCRIPTION
Ba� ery charged, system in opera� on
Func� on test being performed
Endurance test is being performed
Fixture or circuit failure
Endurance test: ba� ery out of order
Ba� ery or circuit failure
Emergency, no more power supply
Opera� ng temp.
0-55˚C
Emergency output
2.5 Wa�
Emergency opera� ng � me
>3 hours
IP-ra� ng
IP40
MANUAL
EMERGENCY LIGHTING MODULE
WITH INVERTER AND BATTERY
BACKUP
IL-DCISET+