Radiografische energiesensor contactdoosadapter
Effective energy
Transmission interval
Rel. threshold value, effective
output
Abs. threshold value, effective
output
Suppression length, effective
output
Averaging length
Information window
During channel selection in the Information window, the following values are displayed.
Display value
Measuring status:
value is real/
out of service
Measuring status:
no fault/
value is corrupted due to failure
82582203
J:0082582203
-1073741823...1073741823
Wh
Basic setting: 0 Wh (Current
value)
1 ... 60 min
Basic setting: 15 min
1 ... 50 %
Basic setting: 10 %
0 ... 2000 W
Basic setting: 1 W
0 ms ... 300 s
Basic setting: 0 ms
0.2 ... 300 s
Basic setting: 1 s
Explanations
value is real: Device being operated
out of service: Device error
no fault: Measurement active
value is corrupted due to failure: The sensor is
not supplying valid measured values.
5/7
Displays the currently cumula-
ted effective energy. The
value can be reset to 0 or set
to any other value.
The current consumption data
is transmitted at the interval
set here at the latest. Changes
to the effective output cause
fresh transmission, however
only after one minute at the
earliest.
The transmission of consump-
tion data can be coupled to
the change in effective output.
The basis is always the most
recently transmitted effective
output value. If the percentage
change entered here is excee-
ded, then all the measured
values are resent.
A lower threshold value of the
effective output can be ente-
red here, to avoid frequent
transmission in the lower
power range. Event-controlled
transmission is only active
above this threshold value.
Triggers for event-controlled
transmission are often switch-
on and switch-off operations.
In order to avoid incorrect
measured values due to
switch-on peaks, this parame-
ter can be used to enter a sup-
pression period. The measu-
red values are only transmit-
ted if the effective output is still
above or below the relative
threshold value after the set
time.
In the case of effective output,
it is not the current value
which is transmitted, as with
other measured values, but
the average value. It is possi-
ble to set the period for avera-
ge value formation here.
14.03.2014