3 User menus
This chapter discusses all settings in the user menu.
3.1 Target temperature
Input range: 0.0°C - 50.0°C [factory value: 20°C]
Here you can set the desired temperature for the department.
3.2 Minimum ventilation
Input range: 0% - 100% [factory value: 10%]
Here you can set the desired minimum ventilation. This is the ventilation rate when the room temperature is
equal to or lower than the set temperature.
3.3 Maximum ventilation
Input range: 5% - 100% [factory value: 100%]
Here you can set the desired maximum ventilation. This is the ventilation rate when the room temperature
has reached the end of the bandwidth.
3.4 Bandwidth
Input range: 1.0°C - 20.0°C [factory value: 5.0°C]
Here you can set the desired temperature range in which the ventilation is increased from minimum to
maximum.