Data type
unsigned
1
Address
int.
unsigned
2
RS485 baud rate
int.
unsigned
3
RS485 Parity mode
int.
unsigned
4
Device type
int.
unsigned
5
HW version
int.
unsigned
6
FW version
int.
7-10
unsigned
11
Mode - Sensor 1
int.
unsigned
12
Range Sensor 1
int.
unsigned
13
Response Time Sensor 1
int.
Max. pressure limit -
unsigned
14
Sensor 1
int.
Min. pressure limit -
unsigned
15
Sensor 1
int.
Power-up timer - Sensor 1 unsigned
16
int.
unsigned int K-factor selection according to the
17
K-factor Sensor 1
18-20
unsigned
21
Mode - Sensor 2
int.
unsigned
22
Range Sensor 2
int.
unsigned
23
Response Time Sensor 2
int.
Max. pressure limit -
unsigned
24
Sensor 2
int.
Min. pressure limit -
unsigned
25
Sensor 2
int.
Power-up timer - Sensor 2 unsigned
26
int.
unsigned int K-factor selection according to the
27
K-factor Sensor 2
28-30
Voor meer info omtrent Modbus over een serieel network, bezoek volgende link: http://www.modbus.org/docs/Modbus_over_serial_line_V1_02.pdf
MIW-SPD-NL-000 - 02 / 07 / 19
Description
Data
Device address
Modbus communication baud rate
Parity check mode
Device type (Read only)
Hardware version of the device
(Read only)
Firmware version of the device (Read
only)
Reserved, return 0
Operating mode of Sensor 1
Range selection for Sensor 1
Response time selection for Sensor
1
Max. pressure limit selection for
Sensor 1
Min. pressure limit selection for
Sensor 1
Power up timer before measuring
the lower limit for Sensor 1
fan / drive type for Sensor 1
Reserved, return 0
Operating mode of Sensor 2
Range selection for Sensor 2
Response time selection - Sensor 2
Max. pressure limit selection for
Sensor 2
Min. pressure limit selection for
Sensor 2
Power up timer before measuring
the lower limit for Sensor 2
fan / drive type for Sensor 2
Reserved, return 0
www.sentera.eu
terug naar inhoudstafel
1—247
1 =
9.600
2 =
19.200
3 =
38.400
0 =
8N1
1 =
8E1
2 =
8O1
SPD-X-2K0 =
1020
SPD-X-6K0 =
1052
XXX
XXX
1 =
Standalone mode
2 =
Modbus mode
SPD-X-2K0
SPD-X-6K0
0 =
0—100 Pa
0 =
0—1.000 Pa
1 =
0—250 Pa
1 =
0—1.500 Pa
2 =
0—500 Pa
2 =
0—2.000 Pa
3 =
0—750 Pa
3 =
0—2.500 Pa
4 =
0—1.000 Pa
4 =
0—3.000 Pa
5 =
0—2.000 Pa
5 =
0—4.000 Pa
6 =
-50—50 Pa
6 =
0—5.000 Pa
7 =
-100—100 Pa
7 =
0—6.000 Pa
0 =
0,5 s
1 =
1 s
2 =
2 s
3 =
5 s
SPD-X-2K0 =
-100—2.000
SPD-X-6K0 =
0—6.000
SPD-X-2K0 =
-100—2.000
SPD-X-6K0 =
0—6.000
0—1.000 s
0—1.000
1 =
Standalone mode
2 =
Modbus mode
SPD-X-2K0
SPD-X-6K0
0 =
0—100 Pa
0 =
0—1.000 Pa
1 =
0—250 Pa
1 =
0—1.500 Pa
2 =
0—500 Pa
2 =
0—2.000 Pa
3 =
0—750 Pa
3 =
0—2.500 Pa
4 =
0—1.000 Pa
4 =
0—3.000 Pa
5 =
0—2.000 Pa
5 =
0—4.000 Pa
6 =
-50—50 Pa
6 =
0—5.000 Pa
7 =
-100—100 Pa
7 =
0—6.000 Pa
0 =
0,5 s
1 =
1 s
2 =
2 s
3 =
5 s
SPD-X-2K0 =
-100—2.000
SPD-X-6K0 =
0—6.000
SPD-X-2K0 =
-100—2.000
SPD-X-6K0 =
0—6.000
0—1.000 s
0—1.000
Default
Values
1
2
0 =
1
1 =
2 =
100 = HW version
100 = FW version
1
4
1
SPD-X-2K0 =
1.000
1.000 =
SPD-X-6K0 =
3.000
SPD-X-2K0 =
0
1.000 =
SPD-X-6K0 =
0
60 s
100 =
0
1
4
1
SPD-X-2K0 =
1.000
1.000 =
SPD-X-6K0 =
3.000
SPD-X-2K0 =
0
1.000 =
SPD-X-6K0 =
0
60 s
100 =
0
8N1
8E1
8O1
1.00
1.00
1.000 Pa
1.000 Pa
100 s
1.000 Pa
1.000 Pa
100 s