Beschrijving van parameters
PARAMETERS METERINSTELLINGEN
Veld
Type
Alias
Modbus ID
AANGEPASTE MEETPARAMETERS
Veld
Name
Modbus register
address
Size (number of
registers)
Size of register
(bytes)
Measurement type
Data format
Modbus operating
code
Bytes ordering
Multiplication
factor
Multiplication
factor register
Mask applied to
the register
18
Meter type: Siemens Sentron iEM, Scheinder Electric 3000 Series,
Scheinder Electric iEM 2000, Kamstrup Multical 403 and Custom
Known or more familiar specified name for sensor or meter given by
the user
Modbus identifier or address set of the meter
Name of custom measure
Modbus register address for the data value
Number of registers to read for the data (by the default 2)
Size of the registers in byte to read the data (by the default 2)
Measure type: Instant power (W), Cooling power (W), Heating power (W),
Total consumption energy (W/h), Total cooling energy (W/h), Total heating
energy (W/h), Voltage (V), Current (A), Name (UTF8) and Model (UTF8)
Data format possible: UTF8, float32, UInt64, UInt32, UInt16, Int64, Int32, Int16
Modbus operating code: Read maintenance logs (3), Read input logs (4)
Bytes data order: Big Endian (most significant byte first) or Little Endian
(less byte first)
Factor for which the data must be multiplied to be in the base unit
system
Register in which is stored the factor multiplication (not always needed)
Mask to apply to register (by default 0xFFFF) (not always needed)
Beschrijving
Beschrijving