Alarms
500 Maximum door open time
600 Control temperature alarm type
0 = Geen
1 = Absoluut
2 = Relatief t.o.v. setpoint
601 Control temperature low alarm
602 Control temperature high alarm
603 Temperature alarm difference
604 Control temperature low alarm delay
605 Control temperature high alarm delay
610 Temperature alarm type
(waarden conform P600)
611 Temperature low alarm
612 Temperature high alarm
613 Temperature low alarm delay
614 Temperature high alarm delay
620 Watch temperature alarm type
(waarden conform P600)
621 Watch temperature low alarm
622 Watch temperature high alarm
623 Watch temperature low alarm delay
624 Watch temperature high alarm delay
630 Control RH alarm type
(waarden conform P600)
631 Control RH low alarm
632 Control RH high alarm
633 RH alarm difference
634 Control RH low alarm delay
635 Control RH high alarm delay
Production
912 Log interval time
995 Software version
996 Serial number
997 Production date
3
Als de deur P500 seconden is geopend wordt een alarm 'Door is open' gegenereerd.
4
Gebruikt voor alle temperatuur alarmen.
5
Parameters P610 .. P614 zij instellingen voor de onafhankelijke alarm thermostaat functie.
6
Parameters P620 .. P624 zij instellingen voor de onafhankelijke waak thermostaat functie.
3
4
5
6
Tabel 2 Overzicht parameters.
Pagina 18 van 34
Documentnr.: 1 7 1 0 10
Bereik
0 - 999
0 - 2
-100 - 100
-100 - 100
0.1 - 10
0 - 999
0 - 999
0 - 2
-100 - 100
-100 - 100
0 - 999
0 - 999
0 - 2
-100 - 100
-100 - 100
0 - 999
0 - 999
0 - 2
-100 - 100
-100 - 100
1 - 100
0 - 999
0 - 999
0 - 120
0 - 0
0 - 0
0 - 0
versie V2.0
Eenh.
Def.
Sec
0
0
°C
-20
°C
60
K
1
Min
0
Min
0
0
°C
-20
°C
60
Min
0
Min
0
0
°C
-20
°C
60
Min
0
Min
0
0
%
0
%
100
%
5
Min
0
Min
0
Min
1
100
100
100