RDCZ
RESIDENTIËLE
VENTILATORSNELHEIDSREGELAAR
HOLDING REGISTERS (Read / write)
Data type
40021
Master / Slave mode
unsigned int.
40022
Temperature setpoint
unsigned int.
40023
CO
setpoint
unsigned int.
2
40024
Air quality setpoint
unsigned int.
40025
Pressure setpoint
unsigned int.
40026
Relative humidity setpoint unsigned int.
40027
Normal / inverse mode
unsigned int.
40028
Disable / Enable PI control unsigned int.
40029
40030
PI control Kp value
unsigned int.
40031
PI control Ki value
unsigned int.
40032
40033
Display mode
unsigned int.
40034
Output overrule timer
unsigned int.
40035-
40040
Nota: De holding registers kunnen zowel uitgelezen als overschreven worden: "Read Holding Registers", "Write single register" en "Write Multiple Registers" commandos.
Voor meer info omtrent Modbus over een serieel network, bezoek volgende link:
MIW-RDCZ-NL-000 - 19 / 10 / 17
Description
Selection of device operating mode
Temperature setpoint in Master mode
CO
setpoint in Master mode
2
Air quality setpoint in Master mode (Sets the content of air
pollutants in kppm)
Pressure setpoint in Master mode
Relative humidity setpoint in Master mode
Output mode selection
Disable / Enable PI control calculation for output
Reserved, returns "0"
Set proportional gain for PI control
Set integral gain for PI control
Reserved, returns "0"
Display input / output value selection
Set overrule timer in case output value has been changed
manually
Reserved, return "0"
http://www.modbus.org/docs/Modbus_over_serial_line_V1_02.pdf
www.sentera.eu
terug naar inhoudstafel
Automatische modus (master)
Data
Default
Values
0 =
0—1
0
1
=
0—700
200
200 =
0—2000
700
700 =
0—2000
700
700 =
0—2000
100
100 =
0—1000
400
400 =
0 =
0—1
0
1 =
0 =
0—1
0
1 =
50 =
0—100
20
20 =
2 =
0—100
20
50 =
20 =
0 =
0—1
0
1 =
Show controller output value
10 =
10—1440
10
1440 =
Slave mode
Master mode
20,0 ºC
0,70 kppm
0,70 kppm
0,10 kPa
40,0 %
normal output
inverse output
Disable
Enable
5,0
2,0
0,2
5,0
2,0
Show sensor input value
10 min
24 h
15 - 16