VFSC9
ELEKTRONISCHE DIGITALE
SNELHEIDSREGELAAR
NOTA
ATTENTIE
MODBUS REGISTER MAPS
INPUT REGISTERS
Data type
30001
Output value
unsigned int.
Minimum value of
30002
unsigned int.
PWM duty cycle
Maximum value of
30003
unsigned int.
PWM duty cycle
30004
Input mode
unsigned int.
30005
Work mode
unsigned int.
HOLDING REGISTERS
40001
Device slave address
40002
Modbus baud rate
40003
Modbus parity mode
40004
Device type
40005
HW version
40006
FW version
40007
40008
Overwrite mode
40009
40010
Modbus registers reset
Minimum value of PWM
40011
duty cycle
Maximum value of PWM
40012
duty cycle
40013
Input mode
MIW-VFSC9-NL-000 - 12 / 07 / 18
Voor FP-versie
1.
Draai de potentiometer op de voorkant van de behuizing naar de 'MAX' positie.
Schakel de input van de externe contact (Di) AAN. De groene LED moet AAN
staan en motor op maximale snelheid gaan draaien.
2.
Draai de potentiometer op de voorkant van de behuizing naar de 'MIN' positie.
3.
De groene LED moet AAN staan en motor op minimale snelheid gaan draaien.
4.
Schakel de input van de externe contact (Di) UIT. De motor moet stoppen.
Als de controller niet volgens deze instructies zoals hierboven werkt, moet men de
bedrading als de instelling van het toestel nazien.
Heet oppervlak! Het oppervlak van het apparaat kan heet worden en
brandwonden veroorzaken bij aanraking. Vermijd contact met het toestel in
werking!
Description
Output value (PWM duty cycle) in %
Minimum value of PWM duty cycle in %
Maximum value of PWM duty cycle in %
Active input
Current work mode
Data type
Description
unsigned int. Modbus device address
unsigned int. Modbus communication baud rate
unsigned int. Parity check mode
unsigned int. Device type (Read only)
unsigned int. Hardware version of the device (Read
only)
unsigned int. Firmware version of the device (Read
only)
unsigned int. Reserved, returns 0
unsigned int. Overwrite mode selection
Reserved, returns 0
unsigned int. Resets all Modbus registers to
default values (except registers 1—3)
unsigned int. Sets minimum PWM duty cycle value
in percentage
unsigned int. Sets maximum PWM duty cycle value
in percentage
unsigned int. Selects active input
www.sentera.eu
terug naar inhoudstafel
Data
Values
0—90
80 =
20— 65
145 =
70—90
80 =
1 =
1—2
2 =
0 =
0—2
1 =
2 =
Data
Default
Values
1—247
1
0 =
1 =
2 =
0—5
2
3 =
4 =
5 =
0 = 8N1
0 =
1 = 8E1
1
1 =
2 = 8O1
2 =
3012
3012 =
0 x 0100
XXXX
0 x 0200
XXXX
0 =
0—1
0
1 =
0 =
0—1
0
1 =
20—65
40
45 =
70—90
90
80 =
0 =
0—2
0
1 =
2 =
80%
45 %
80%h
Analog input
External potentiometer input
STOP
RUN
ALARM / TK
4.800 bps
9.600 bps
19.200 bps
38.400 bps
57.600 bps
115.200 bps
None
Even
Odd
VFSC9-XX
HW version 1.00
=
FW version 2.00
=
Inactive
Active
Idle
Reset
45% PWM
80% PWM
Auto
Analog input
External potentiometer
input
11 - 12