Sentera Controls DPS-M-2 Montagehandleiding pagina 12

Verberg thumbnails Zie ook voor DPS-M-2:
Inhoudsopgave

Advertenties

DPS-M -2
HOLDING REGISTERS
Data type
1
Device slave address
unsigned int. Modbus device address
2
Modbus baud rate
unsigned int. Modbus communication baud rate
3
Modbus parity mode
unsigned int. Parity check mode
4
Device type
unsigned int. Device type (Read-only)
5
HW version
unsigned int. Hardware version of the device (Read-only)
6
FW version
unsigned int. Firmware version of the device (Read-only)
7-10
11
Minimum pressure range
unsigned int. Minimum of the pressure range
12
Maximum pressure range
unsigned int. Maximum of the pressure range
13
Minimum pressure alert
unsigned int. Minimum differential pressure alarm value
14
Maximum pressure alert
unsigned int. Maximum differential pressure alarm value
15
Minimum volume flow range high unsigned int.
16
Minimum volume flow range low unsigned int.
Maximum volume flow range
17
unsigned int.
high
18
Maximum volume flow range low unsigned int.
19
Minimum volume flow alert high unsigned int.
20
Minimum volume flow alert low
unsigned int.
Maximum volume flow alert
21
unsigned int.
high
Maximum volume flow alert
22
unsigned int.
low
23
Minimum air velocity range
unsigned int. Minimum air velocity range value
24
Maximum air velocity range
unsigned int. Maximum air velocity range value
25
Minimum air velocity alert
unsigned int. Minimum air velocity alarm value
26
Maximum air velocity alert
unsigned int. Maximum mum air velocity alarm value
27
28
Response time
unsigned int. Response time selection
29
Power-up timer
unsigned int.
30
K-factor.
unsigned int.
unsigned
31
Output type
int
Modbus network resistance
32
unsigned int. Sets device as an end device on the line
terminator (NBT)
33
Altitude
unsigned int. Current altitude
34
Pitot air velocity
unsigned int. Enables Air Velocity Readout.
35
Duct cross sectional area [ cm
]
unsigned int.
2
36
37
Measurement readout
unsigned int. 4-digit measurement indication ON / OFF
38
Operating mode
unsigned int. Operating mode selection
39
40
Recalibrate sensor
unsigned int. Sensor recalibration
41-49
50
Modbus registers reset
unsigned int.
Voor meer info omtrent Modbus over een serieel network, bezoek volgende link:
(1)
Gebruik de PSET-QF of PSET-PVC-set om het drukverschil te meten;
(2)
Om het debiet van de luchtstroom te meten met gebruik van PSET-PTx, geef het doorsnede-oppervlak van de buis \ [cm²] in Modbus-register 35. Om het debiet van de
luchtstroom te meten met gebruik van PSET-GF of PSET-PVC, geef het doorsnede-oppervlak van de buis \ [cm²] in Modbus-register 30.
(3) Gebruik de PSET-PTx-set om luchtsnelheid te meten.
MIW-DPS-M-2-NL-000 - 20 / 12 / 18
VERSCHILDRUKTRANSMITTER
Description
Reserved, return 0
Minimum volume flow range value
Maximum volume flow range value
Minimum volume flow alarm value
Maximum volume flow alarm value
Reserved, returns 0
Power-up timer before setting alert and
range limit flags.
K-factor according to motor / fan
specifications
Select analog / digital output type1
Calculation of the Volume Flow Rate when
K-factor is not known
Reserved, returns 0
Reserved, returns 0
Reserved, return 0
Reset Modbus Holding Registers to
default values
http://www.modbus.org/docs/Modbus_over_serial_line_V1_02.pdf
www.sentera.eu
terug naar inhoudstafel
Data
0 =
1 =
2 =
DPS-M-1K0 -2 =
DPS-M-2K0 -2 =
DPS-M-4K0 -2 =
DPS-M-10K -2 =
0 - (Max. pressure range - 50 Pa)
DPS-M-1K0 -2
(Min. pressure range + 50 Pa) - 1.000
DPS-M-2K0 -2
(Min. pressure range + 50 Pa) - 2.000
DPS-M-4K0 -2
(Min. pressure range + 50 Pa) - 4.000
DPS-M-10K -2
(Min. pressure range + 50 Pa) - 10.000
Min pressure range - max. pressure alarm
Min pressure
alarm—max.
pressure
range
0 - (Maximum volume flow range -10 m³/h)
DPS-M-1K0 -2
(Min. vol. flow range + 10 m³/h) - 25.000
DPS-M-2K0 -2
(Min. vol. flow range + 10 m³/h) - 40.000
DPS-M-4K0 -2
(Min. vol. flow range + 10 m³/h) - 100.000
DPS-M-10K -2
(Min. vol. flow range + 10 m³/h) - 180.000
Min. volume flow range - max. volume flow alarm
Min. volume flow alarm - max.
volume flow range
0 - (Max. air velocity range - 1 m/s)
(Min. air velocity range +1 m/s) - 300
Min. air velocity range—Max. air velocity alarm
Min. velocity alarm—Max. air velocity range
Default
Values
1—247
1
0 =
1 =
2 =
0—6
2
3 =
4 =
5 =
6 =
8N1
0 =
8E1
1
1 =
8O1
2 =
1075
1076
1077
1078
XXX
0x0100 =
HW version 1.00
XXX
0x0110 =
FW version 1.10
10 =
0
100 =
1.000
2.000
100 =
4.000
10.000
10 =
0
100,0 Pa (DPS-M-
100 =
DPS-X-1K0 -2
1.000
DPS-X-2K0 -2
2.000
100=
DPS-X-2K0 -2
4.000
1000=
DPS-X-10K -2
10.000
0
10 =
25.000
40.000
20.000 =
100.000
180.000
0
1.000 =
DPS-X-1K0 -2
25.000
DPS-X-2K0 -2
40.000
10.000 =
DPS-X-4K0 -2
100.000
DPS-X-10K -2
180.000
0
100 =
300
300 =
0
100 =
300
300 =
1—100
10
10 =
0—1.000
60 s
100 =
0—1.000
0
1
1—3
1
2
0—100% PWM,
3
0 =
NBT disconnected
0—1
0
1 =
NBT connected
0—5.000
0
1.000 =
0 =
0—1
0
1 =
0 =
0—32.000
0
100 =
0 =
LED display off
0—1
1
1 =
LED display on
1 =
1—3
1
2 =
Volume flow rate
3 =
0 =
0—1
0
1 =
0 =
0—1
0
Reset Modbus
1 =
4.800
9.600
19.200
38.400
57.600
115.200
230.400
None
Even
Odd
10 Pa
100 Pa
100 Pa
10 Pa
10K -2)
100 Pa
1000 Pa
10 m³/h
20.000 m³/h
1.000 m³/h
10.000 m³/h
10,0 m/s
30,0 m/s
10,0 m/s
30,0 m/s
1,0 s
100 s
0—10 VDC
0—20 mA
1.000 m
Disabled
Enabled
Not used
100 cm
2
Differential
pressure
(1)
(2)
Air velocity
(3)
Inactive
Active
Idle
Registers
12 - 16