DPS-X -2
HOLDING REGISTERS
Data type
1
Device slave address
unsigned int.
2
Modbus baud rate
unsigned int.
3
Modbus parity mode
unsigned int.
4
Device type
unsigned int.
5
HW version
unsigned int.
6
FW version
unsigned int.
7-10
11
Minimum pressure range
unsigned int.
12
Maximum pressure range
unsigned int.
13
Minimum pressure alert
unsigned int.
14
Maximum pressure alert
unsigned int.
15
Minimum volume flow range high unsigned int.
16
Minimum volume flow range low unsigned int.
Maximum volume flow range
17
unsigned int.
high
18
Maximum volume flow range low unsigned int.
19
Minimum volume flow alert high unsigned int.
20
Minimum volume flow alert low
unsigned int.
Maximum volume flow alert
21
unsigned int.
high
Maximum volume flow alert
22
unsigned int.
low
23
Minimum air velocity range
unsigned int.
24
Maximum air velocity range
unsigned int.
25
Minimum air velocity alert
unsigned int.
26
Maximum air velocity alert
unsigned int.
27
28
Response time
unsigned int.
29
Power-up timer
unsigned int.
30
K-factor.
unsigned int.
31
Output type
unsigned int.
Modbus network resistance
32
unsigned int.
terminator (NBT)
33
Altitude
unsigned int.
34
Pitot air velocity
unsigned int.
35
Duct cross sectional area [ cm
]
unsigned int.
2
36
37
Measurement readout
unsigned int.
38
Operating mode
unsigned int.
39
Internal voltage source selection unsigned int.
40
Recalibrate sensor
unsigned int.
Voor meer info omtrent Modbus over een serieel network, bezoek volgende link:
(1)Gebruik de PSET-QF of PSET-PVC-set om het drukverschil te meten;
(2) Om het debiet van de luchtstroom te meten met gebruik van PSET-PTx, geef het doorsnede-oppervlak van de buis \ [cm²] in Modbus-register 35. Om het debiet van de luchtstroom te
meten met gebruik van PSET-GF of PSET-PVC, geef het doorsnede-oppervlak van de buis \ [cm²] in Modbus-register 30.
(3) Gebruik de PSET-PTx-set om luchtsnelheid te meten.
MIW-DPS-X-2-NL-000 - 20 / 12 / 18
VERSCHILDRUKTRANSMITTER
Description
Modbus device address
Modbus communication baud rate
Parity check mode
Device type (Read-only)
Hardware version of the device (Read-
only)
Firmware version of the device (Read-
only)
Reserved, return 0
Minimum of the pressure range
Maximum of the pressure range
Minimum differential pressure alarm
value
Maximum differential pressure alarm
value
Minimum volume flow range value
Maximum volume flow range value
Minimum volume flow alarm value
Maximum volume flow alarm value
Minimum air velocity range value
Maximum air velocity range value
Minimum air velocity alarm value
Maximum mum air velocity alarm value
Reserved, returns 0
Response time selection
Power-up timer before setting alert and
range limit flags.
K-factor according to motor / fan
specifications
Analogue / modulating output type
Sets device as an end device on the line
Current altitude
Enables Air Velocity Readout.
Calculation of the Volume Flow Rate
when K-factor is not known
Reserved, returns 0
4-digit measurement indication ON / OFF
Operating mode selection
Selection of internal voltage source for
PWM
Sensor recalibration
http://www.modbus.org/docs/Modbus_over_serial_line_V1_02.pdf
www.sentera.eu
terug naar inhoudstafel
Data
0 =
1 =
2 =
DPS-X-1K0 -2 =
DPS-X-2K0 -2 =
DPS-X-4K0 -2 =
DPS-X-10K -2 =
0 - (Max. pressure range - 50 Pa)
DPS-X-1K0 -2
(Min. pressure range + 50 Pa) - 1.000
DPS-X-2K0 -2
(Min. pressure range + 50 Pa) - 2.000
DPS-X-4K0 -2
(Min. pressure range + 50 Pa) - 4.000
DPS-X-10K -2
(Min. pressure range + 50 Pa) - 10.000
Min pressure range - max. pressure alarm
Min pressure
alarm—max.
pressure
range
0 - (Maximum volume flow range -10 m³/h)
DPS-X-1K0 -2
(Min. vol. flow range + 10 m³/h) - 25.000
DPS-X-2K0 -2
(Min. vol. flow range + 10 m³/h) - 40.000
DPS-X-4K0 -2
(Min. vol. flow range + 10 m³/h) - 100.000
DPS-X-10K -2
(Min. vol. flow range + 10 m³/h) - 180.000
Min. volume flow range - max. volume flow alarm
Min. volume flow alarm - max.
volume flow range
0 - (Max. air velocity range - 1 m/s)
(Min. air velocity range +1 m/s) - 300
Min. air velocity range—Max. air velocity alarm
Min. velocity alarm—Max. air velocity range
Default
Values
1—247
1
0 =
1 =
2 =
0—6
2
3 =
4 =
5 =
6 =
8N1
0 =
8E1
1
1 =
8O1
2 =
1075
1076
1077
1078
0x0100
XXX
= HW version 1.00
0x0110
XXX
FW version 1.10
=
10 =
0
100 =
1.000
2.000
100 =
4.000
10.000
10 =
0
100 = 100,0 Pa (DPS-X-
DPS-X-1K0 -2
1.000
DPS-X-2K0 -2
2.000
100 =
DPS-X-2K0 -2
4.000
1000 =
DPS-X-10K -2
10.000
0
10 =
25.000
40.000
20.000
20.000 m³/h
100.000
=
180.000
0 1.000 =
DPS-X-1K0 -2
25.000
DPS-X-2K0 -2
40.000
10.000
10.000 m³/h
DPS-X-4K0 -2
100.000
=
DPS-X-10K -2
180.000
0
100 =
300
300 =
0
100 =
300
300 =
1—100
10
10 =
0—1.000
60 s
100 =
0—1.000
0
1 =
1—3
1
2 =
3 =
0 =
0—1
0
disconnected
1 =
NBT connected
0—5.000
0 1.000 =
0 =
0—1
0
1 =
0 =
0—32.000
0
100 =
0 =
LED display off
0—1
1
1 =
LED display on
1 =
1—3
1
2 =
Volume flow
3 =
Air velocity
0 =
0—1
0
1 =
0 =
0—1
0
1 =
4.800
9.600
19.200
38.400
57.600
115.200
230.400
None
Even
Odd
10 Pa
100 Pa
100 Pa
10 Pa
10K -2)
100 Pa
1000 Pa
10 m³/h
1.000 m³/h
10,0 m/s
30,0 m/s
10,0 m/s
30,0 m/s
1,0 s
100 s
0—10 VDC
0—20 VDC
PWM
NBT
1.000 m
Disabled
Enabled
Not used
100 cm
2
Differential
pressure
(1)
rate
(2)
(3)
3,3 VDC
12 VDC
Inactive
Active
13 - 16