6.APPENDIX
6.2 Specificatie kabel
(1) Enkele fase-unit
Naamplaat
maximaal
Faselijn
Stroom
Niet meer
2×1.5mm
dan 10A
2×2.5mm
10~16A
16 ~25A
2×4mm
25 ~32A
2×6mm
32 ~40A
2×10mm
40 ~63A
2×16mm
2×25mm
63~75A
2×25mm
75~101A
2×35mm
101~123A
123~148A
2×50mm
148~186A
2×70mm
186~224A
2×95mm
(2) Driefase-unit
Naamplaat
maximaal
Faselijn
Stroom
Niet meer
3×1.5mm
dan 10A
3×2.5mm
10~16A
16 ~25A
3×4mm
25 ~32A
3×6mm
32 ~40A
3×10mm
40 ~63A
3 ×16mm
3 ×25mm
63~75A
3×25mm
75~101A
3×35mm
101~123A
3×50mm
123~148A
3×70mm
148~186A
186~224A
3×95mm
Wanneer de unit buiten wordt geïnstalleerd, gebruik dan de kabel die tegen UV kan.
Aardleiding
MCB
2
2
1.5mm
20A
2
2
2.5mm
32A
2
2
4mm
40A
2
2
40A
6mm
2
2
63A
10mm
2
2
80A
16mm
2
2
100A 30mA minder dan 0.1 sec
25 mm
2
2
125A 30mA minder dan 0.1 sec
25 mm
2
2
35mm
160A 30mA minder dan 0.1 sec
2
2
50mm
225A 30mA minder dan 0.1 sec
2
2
70mm
250A 30mA minder dan 0.1 sec
2
2
95mm
280A 30mA minder dan 0.1 sec
Aardleiding
MCB
2
2
1.5mm
20A
2
2
2.5mm
32A
2
2
4mm
40A
2
2
6mm
40A
2
2
63A
10mm
2
2
80A
16mm
2
2
100A 30mA minder dan 0.1 sec
25 mm
2
2
125A 30mA minder dan 0.1 sec
25 mm
2
2
160A 30mA minder dan 0.1 sec
35mm
2
2
50mm
225A 30mA minder dan 0.1 sec
2
2
70mm
250A 30mA minder dan 0.1 sec
2
2
95mm
280A 30mA minder dan 0.1 sec
Creepage-beschermer
30mA minder dan 0.1 sec
30mA minder dan 0.1 sec
30mA minder dan 0.1 sec
30mA minder dan 0.1 sec
30mA minder dan 0.1 sec
30mA minder dan 0.1 sec
Creepage-beschermer
30mA minder dan 0.1 sec
30mA minder dan 0.1 sec
30mA minder dan 0.1 sec
30mA minder dan 0.1 sec
30mA minder dan 0.1 sec
30mA minder dan 0.1 sec
35
Signaalleidin
g
n × 0.5mm 2
Signaalleidin
g
n × 0.5mm 2