Handleiding DP-4000-PROFIBUS® PA
Block Type
Function Block
Transducer Block
Physical Block
Physical Block Parameters (Slot 0)
In de onderstaande tabel worden de Physical Block parameters beschreven.
Index Name
16
BLOCK_OBJECT
Reserved
Block_Object
Parent_Class
Class
Dev_Rev
Dev_Rev_Comp
DD_Revision
Profile
Profile_Revision
Execution_Time
Number_of_Parameters
Address_of_View_1
Number_of_Views
17
ST_REV
18
TAG_DESC
19
STRATEGY
20
ALERT_KEY
21
TARGET_MODE
22
MODE_BLK
Actual_mode
Permitted_mode
Normal_mode
23
ALARM_SUM
Current
Unacknowledged
Unreported
Disabled
24
SOFTWARE_REVISION
25
HARDWARE_REVISION
NL-4000-DP-PROFIBUS PA-04-2023-02
Description
Control system behavior like for example: Analog Input,
Analog Output, Discrete Input, Discrete Output and
Totalizer.
Converting mapping between process data and Function
Blocks. The Transducer Block is used to perform
preprocessing and calibration parameters of device data
according to specific device settings. At least one Transducer
Block has to be available for a PROFIBUS® PA field device.
Describes the specific data identifying the individual physical
device properties such as the device name, manufacturer,
and serial number.
Type
Description
Record
Block object
Unsigned8
0
Unsigned8
0x01, physical block
Unsigned8
0x01, Transmitter
Unsigned8
250, not used
Unsigned16
1
Unsigned16
1
Unsigned16
0
MSB: 0x40 -> Number of the PROFIBUS PA profiles
OctetString(2)
within PI Profile Class 64
LSB: 0x02 -> Class B
Unsigned16
0x302: PA Prfile Revision 3.02
Unsigned8
0
Unsigned16
29, number of parameters
Unsigned16
0x00F8, View_1 has an index 248
Unsigned8
1, only one View_1 in Device
ST_REV shall be incremented at least by one if at
Unsigned16
least one static parameter in the corresponding
block has been modified
OctetString(32)
Unsigned16
Unsigned8
Unsigned8
Target mode
Record
Unsigned8
Actual mode
Unsigned8
Permitted mode
Unsigned8
Normal mode
Record
OctetString(2)
Current alarm
OctetString(2)
Unacknowledged alarm
OctetString(2)
Unreported alarm
OctetString(2)
Disabled alarm
VisibleString(16)
Revision-number of the software of the field device
VisibleString(16)
Revision-number of the hardware of the field device
Page 27