DETECT IAQ

Holding registers

Register
Parameter description
40001
Y1 output overdrive
40002
Y2 output overdrive
40003
Y3 output overdrive
40004
Y4 output overdrive
40005
CO
measurement tuning (offset)
2
40006
Temperature measurement tuning (offset)
40008
Control method
40009
Controller output
40010
Set point, CO
40011
Set point, temperature
40013
Proportional band, CO
40014
Proportional band, temperature
40016
Integration time
40035
PIR activation delay
*
40036
PIR deactivation delay
*
40038 /
Y1...Y4 output range
40027
**
40039 /
Fixed control output
40028
**
40040 /
Fixed control output timer
40029
**
DETECT IAQ OCSa CO
-TEMP-MB
*
2
DETECT IAQ Da CO
-TEMP-MB
**
2
10
Swegon behoudt zich het recht voor om specificaties te wijzigen.
2
2
Data type
Values
Signed 16
0...1000
Signed 16
0...1000
Signed 16
0...1000
Signed 16
0...1000
Signed 16
-200...200
Signed 16
-30...30
Signed 16
0 - 1
Signed 16
0 - 1 - 2 - 3 - 4
Signed 16
400...10000
Signed 16
180...260
Signed 16
100...10000
Signed 16
10...320
Signed 16
50...5000
Signed 16
0 - 1 - 2
Signed 16
0 - 1 - 2 - 3 - 4 - 5
Signed 16
0 - 1 - 2
Signed 16
0 - 1 - 2 - 3 - 4 - 5
Signed 16
0 - 1 - 2 - 3
20230206
Range
Default
0...10.00 V
0
0...10.00 V
0
0...10.00 V
0
0...10.00 V
0
-200...200 ppm
0
-3.0...3.0 °C
0
0: P
1
1: PI
0: OFF
4
1: CO
2
2: TEMPERATURE
4: MAXIMUM CTRL
400...10000 ppm
700
18.0...26.0 °C
210
100...10000 ppm
500
1.0...32.0 °C
20
50...5000 s
300
0: 0 min
1
1: 3 min
2: 6 min
0: 5 min
1
1: 15 min
2: 30 min
3: 60 min
4: 90 min
5: 120 min
0: 0...10 V
0
1: 2...10 V
2: 0...5 V
0: OFF
0
1: 100%
2: 75%
3: 50%
4: 25%
5: 0%
0: 6 h
1
1: 12 h
2: 24 h
3: Manual