Modbus Register Mappen - Sentera Controls MVSS Montagehandleiding

Inhoudsopgave

Advertenties

MVSS
ELECTRONISCHE VENTILATOR SNELHEIDSREGELAAR,
MET TK VOOR DIN-RAIL MONTAGE

MODBUS REGISTER MAPPEN

INPUT REGISTERS
Data type
1
Analog input level
unsigned int.
Current output
2
unsigned int.
voltage
3
Analog input type
unsigned int.
Ascending /
4
descending input
unsigned int.
mode
Maximum output
5
unsigned int.
voltage
Minimum output
6
unsigned int.
voltage
7
Enable off level
unsigned int.
8
Off level value
unsigned int.
Kick start / soft
9
unsigned int.
start
Remote control
10
unsigned int.
input
12
L1 control
unsigned int.
13
Alarm LED
unsigned int.
14
ON/Stand-by LED
unsigned int.
15-20
MIW-MVSS-NL-002 - 10 / 11 / 22
Description
Analog input value depending on the selected analog input
type
Actual output voltage
Type of the selected analog input
Ascending or descending analog input mode depending on
the selected analog input type.
Maximum output voltage
Minimum output voltage
Enables off level
Off level value depending on the selected analog input type
and ascending / descending analog input mode.
Selects kick start or soft start
Remote control input
L1 control
Alarm LED
ON/Stand-by LED
Reserved, returns 0
www.sentera.eu
terug naar inhoudstafel
Data
Values
0 =
0 VDC
100 =
10,0 VDC
0—100
0 =
0 mA
100 =
20,0 mA
0 =
0 % Us
0,
30 =
30 % Us
30—100
100 =
100 % Us
0 =
0—20 mA
0—1
1 =
0—10 VDC
0 =
10—0 VDC
1 =
0—10 VDC
0—1
0 =
20—0 mA
1 =
0—20 mA
75 =
75 % Us
75—100
100 =
100 % Us
30 =
30 % Us
30—70
70 =
70 % Us
0 =
Disabled
0—1
1 =
Enabled
Ascending mode:
Voltage
0 =
0 VDC
400 =
4,0 VDC
Current
0 =
0 mA
200 =
8,0 mA
0 — 40
60—100
Descending mode:
Voltage
100 =
10,0 VDC
60 =
6,0 VDC
Current
100 =
20,0 mA
60 =
12,0 mA
0 =
Soft start
0—1
1 =
Kick start
0 =
Disabled
0—1
1 =
Enabled
0 =
0—1
1 =
0 =
0—1
1 =
0 =
0—2
1 =
2 =
Stand-by
12 - 17
or
or
Off
On
Off
On
Off
On