14
|
Over de units en opties
CAUTION
Caution when servicing the switch box
1. Before obtaining access to terminal devices, all supply circuits must be interrupted because units at standstill
2. Be aware that temperature of switch boxes can be extremely high.
3. Do not touch the switch box for another 10 minutes after turning off the circuit breaker. Even after 10 minutes,
4. After confirming the main circuit capacitor voltage drop, pull out the outdoor unit fan connector. Make sure not
Caution when performing other servicing
Do never connect power supply cables to compressors (U,V,W) directly. The compressor may burn out.
CAUTION
Caution when servicing the switch box
1. Before obtaining access to terminal devices, all supply circuits must be interrupted because units at standstill
2. Be aware that temperature of switch boxes can be extremely high.
3. Do not touch the switch box for another 10 minutes after turning off the circuit breaker. Even after 10 minutes,
4. After confirming the main circuit capacitor voltage drop, pull out the outdoor unit fan connector. Make sure not
Caution when performing other servicing
Do never connect power supply cables to compressors (U,V,W) directly. The compressor may burn out.
Uitgebreide handleiding voor de installateur en de gebruiker
46
WARNING
may be in a pre-heating mode and start automatically.
always measure the voltage at the terminals of main circuit capacitor or electrical parts and make sure that
those voltages are 50 V DC or less. (Always touch the earth terminal first before pulling out or plugging in
connectors in order to discharge static electricity. This to prevent the PCB from being damaged.)
to touch any live parts during this action. (Strong adverse winds which let the outdoor unit fan rotate, induce
a risk of electrical shock because the fan rotation makes the capacitor store electricity.)
Label op capacity up unit:
WARNING
may be in a pre-heating mode and start automatically.
always measure the voltage at the terminals of main circuit capacitor or electrical parts and make sure that
those voltages are 50 V DC or less. (Always touch the earth terminal first before pulling out or plugging in
connectors in order to discharge static electricity. This to prevent the PCB from being damaged.)
to touch any live parts during this action. (Strong adverse winds which let the outdoor unit fan rotate, induce
a risk of electrical shock because the fan rotation makes the capacitor store electricity.)
Tekst op waarschuwingslabel
Warning
Electric shock caution
Caution when servicing the switch box
ELECTRIC SHOCK CAUTION
N1
P1
Fanmotor connectors:
X1A,X2A / X3A,X4A / X5A,X6A
ELECTRIC SHOCK CAUTION
N1
P1
Fanmotor connectors:
X1A,X2A
Vertaling
Waarschuwing
Waarschuwing voor elektrische
schokken
Let op bij servicewerkzaamheden aan
de schakelkast
4P623521-1B
4P623521-2B
LRYEN10A7Y1+LRNUN5A7Y1
CO₂ Conveni-Pack buitenunit
4P605460-1 – 2020.08