FACTORY SETTINGS
Parameter
Regulating mode
THs
Operating mode
Set-point reduction percentage
Type of external analogue signal
Twin operating mode
Pump start control
12.
TYPES OF ALARM
Alarm Code
Alarm Symbol
E0 - e16; e21
E17 - e19
e20
E22 - e31
E32 - e35
e37
21
"Delete Alarms Log?"
Pressing OK (left button) deletes the alarms memorised
in the log.
On page 12.0 you can set the system status in ON, OFF
or controlled by a remote signal EXT (digital input IN1).
If ON is selected the pump is always on.
If OFF is selected the pump is always off.
If EXT is selected, reading of the status of digital input
IN1 is enabled. When input IN1 is energised the system
goes ON and the pump is started (on the Home Page the
messages "EXT" and "ON" appear alternately at bottom
right); when input IN1 is not energised the system goes
OFF and the pump goes off (on the Home Page the
messages "EXT" and "OFF" appear alternately at bottom
right).
For the connection of the inputs see par. 6.2.1
Value
= Proportional differential pressure regulation
50 ºC
auto
50 %
0-10V
= Alternate every 24h
EXT (from remote signal on input IN1).
Table 6: Factory settings
Alarm Description
Internal Error
Short Circuit
Voltage Error
Internal Error
Electronic system excess temperature
Low voltage
e38
E39 - e40
E43; e44; e45; e54
e46
e42
e56
e57
e58
Tabella 7: Elenco allarmi
INFORMATION
Frequently asked questions (faq) on the ecodesign directive 2009/125/ec establishing a
framework for the setting of ecodesign requirements for energy-related products and its
implementing
regulations:
http://ec.europa.eu/enterprise/policies/sustainable-
business/documents/eco-design/guidance/files/20110429_faq_en.pdf
Guidelines accompanying commission regulations implementing the ecodesign directive:
http://ec.europa.eu/energy/efficiency/ecodesign/legislation_en.htm
"circulators".
13.
ERROR CONDITION AND RESET
Display
Description
indication
E0 – e16
Internal error
Low mains voltage
E37
(LP)
High mains voltage
E38
(HP)
High voltage
Pump blocked
Pressure Sensor
Pump Disconnected
Dry operation
Motor excess temperature (motor protector trips)
Frequency of PWM external signal less than 100 Hz
Frequency of PWM external signal greater than 5 kHz
-
Reset
-
Switch off system power.
-
Wait for the warning lights on the control panel to
go off, then power the system again.
-
If the error persists, change the circulator.
-
Switch off system power.Wait for the warning
lights on the control panel to go off, then power
the system again.
-
Check that the mains voltage is correct, if
necessary reset it at the plate values
-
Switch off system power.
-
Wait for the warning lights on the control panel to
go off, then power the system again.
see