The rotation speed may be set from the display or by an external signal 0-10V or PWM.
Regulation indicated for heating and conditioning plants with constant flow.
8.1.4.
Regulation with constant and proportional differential pressure depending
on the water temperature
9.
CONTROL PANEL
The functions of EVOPLUS circulators can be modified by means of the control panel on the
cover of the electronic control device.
On the panel there are: a graphic display, 4 navigation keys and 3 LED warning lights (see
Figure 10).
9.1.
Graphic Display
Using the graphic display it will be possible to navigate in an easy and intuitive menu which
will enable you to check and modify the system operating mode, the enabling of the inputs
and the working set-point. It will also be possible to view the system status and the log of any
alarms memorised by the system.
9.2.
Navigation Buttons
4 buttons are provided for navigating in the menu: 3 buttons under the display and 1 at the
side. The buttons under the display are called active buttons and the one at the side is called
hidden button. Each page of the menu is made in such a way as to indicate the function
associated with the 3 active buttons (the ones under the display).
In this regulating mode the regulating set point Hs
is reduced or increased according to the water
temperature. THs may be set from 0ºC to 100 ºC
in order to allow operation in both heating and
conditioning plants.
Regulation indicated for:
Plants with variable flow (two-pipe heating plants),
where a further reduction of the circulator
performance is ensured depending on the lowering
of the temperature of the circulating liquid, when
the demand for heating is lower.
Plants with constant flow (single-pipe and
underfloor heating plants), where the circulator
performance can be regulated only by activating
the temperature influence function.
9.3.
Warning Lights
Yellow light: System live signal.
If lit, it means that the system is live.
Never remove the cover if the yellow light is lit.
Red light: Warning of an alarm/malfunction present in the system.
If the light is blinking it is a non-blocking alarm and the pump can still be controlled. If the light
is fixed it is a blocking alarm and the pump cannot be controlled.
Green light: Pump ON/OFF signal.
if lit, the pump is running. If off, the pump is stopped..
10.
MENUS
EVOPLUS circulators offer 2 menus: user menu and advanced menu.
The user menu is accessible from the Home Page by pressing and releasing the central
"Menu" button.
The user menu is accessible from the Home Page by holding down the central "Menu" button
for 5 seconds.
Below are shown the user menu pages with which it is possible to check the system status
and modify its settings.
Instead on the advanced menu there are the configuration parameters for communication
with
MODBUS
systems
(for
http://www.dabpump.com/evoplus). To leave the advanced menu you must scroll through
all the parameters using the central button.
If the menu pages show a key at bottom left it means that it is not possible to change the
settings. To unblock the menus go to the Home Page and press the hidden button and the
button under the key at the same time until the key disappears.
If no button is pressed for 60 minutes, the settings are automatically blocked and the
display switches off. When any button is pressed the display lights up again and the
"Home Page" appears.
To navigate in the menus, press the central button.
To return to the previous page, hold down the hidden button, then press and release the
central button.
To modify the settings use the left and right buttons.
To confirm the change of a setting, hold down the central button "OK" for 3 seconds.
Confirmation will be indicated by the following icon::
ENGLISH
further
details
visit
the
GB
link:
18